Instruction Manual
RECmax Lpd
7.- TECHNICAL FEATURES
Power supply
Rated voltage
230 V ~ ± 30%
Frequency
50 / 60 Hz
Power
5 VA
Uimp
4kV
Installation category
CAT III 300V
Earth leakage protection
Sensitivity, I
∆
n
30 mA - 0.1 A - 0.3 A - 0.5 A - 1 A (programmable)
Trip delay (IEC 60947-2-M)
Programmable
External earth leakage transformer
CIRCUTOR compatible type
WG / WGS / WGC
Internal diameters (mm)
20 - 25 - 30 - 35
Rated current, In ( 4 poles)
63 A
Trip current, I∆n
30 mA
Maximum current, Imax
378 A
All the live conductors feeding the load to be protected must pass through the core of the earth leakage
transformer. The earth protection conductor must never pass through the earth leakage transformer.
Circuit breaker protection
Rated current� In
6 - 10 - 16 - 20 - 25 - 32 - 40 - 50 - 63 A ~
Rated voltage, Un
240 / 415 V ~
Magnetic trip curves
C / D
Cross-section
Flexible cable
Rigid cable
25 mm
2
35 mm
2
Number of poles
RECmax Lpd 2-pole
RECmax Lpd 4-pole
2
4
Residual earth leakage current
0.851
I
∆
n
Breaking capacity (EN 60898)
Poles
Voltage
Icn / Ics
1 - 4
230 / 400 V
6 kA
Breaking capacity (EN 60947-2)
Poles
Voltage
Icu / Ics
2
< 125 V
30 kA
Breaking capacity (EN 60947-2)
~
Poles
Voltage
Icu
2
127 V
30 kA
240 V
20 kA
415 V
10 kA
4
240 V
20 kA
415 V
10 kA
Automatic reclosing
Successive attempts by earth leakage
programmable (by default: 10)
Successive attempts by circuit breaker
programmable (by default: 2)
Timer between successive attempts
programmable (by default: 3 min.)
Meter reset time after last reclosing
programmable (by default: 30 min.)