MEG-1000
Page nº 14
Output relays
Relays: ALARM (15-16-18) and NORMAL (25-26-28).
Type: mechanical, 3 terminals, free of voltage.
Use: AC11 250 V/8 A
Isolation
between contacts: 1000 Va.c.
between coil and contacts: 4000 Va.c.
Relays temporisation adjustment
ALARM relay: from 0.1 to 3 s.
NORMAL relay: from 0.1 to 30 s.
Accuracy:
±
10 %.
Isolation
Between any connection terminal and the case: 2.5 kV 50 Hz for 1 min.
Insulating resistance between the inputs, the outputs and the power supply:
1 G
Ω
.
Insulating resistance between any connection terminal and the case: 1 G
Ω
.
Working conditions
Working temperature: -20 / +50ºC.
Use: indoor.
Constructive characteristics
Case material: ABS self-extinguishing (as per UL 94 V1) and high resistance
against impacts.
Protection degree: Case: IP 52 / Terminals: IP 20
Screwed transparent cover for the adjustment push buttons.
Safety
Category I , EN-61010.
Standards
IEC 255-5, IEC 1010-1, EN 61010-1, IEC 801-2, IEC 801-3, IEC 801-4.