MEG-1000
Page nº 11
The pointer and the scale leds (k
Ω
(2) and M
Ω
(3)) show the delay time when it is
being adjusted:
-
ALARM relay temporisation. Each 100 k
Ω
means a trip delay of 1
second. The active measuring scale is the k
Ω
scale. The adjusting range
is within 0.1 and 3 s.
-
NORMAL relay temporisation. If the active measuring scale is the k
Ω
scale, each 100 k
Ω
means a trip delay of 1 second. If the active
measuring scale is M
Ω
, each 1 M
Ω
means a trip delay of 10 seconds.
The adjusting range is within 0.1 and 30 s.
Adjustment push buttons give access to different adjustments according to the
following sequence: