21
Instruction Manual
line-M
Table 9: Variable codes for Output programming (Table 1)�
Parameter
Phase
Code
Phase
Code
Phase
Code
Phase
Code
Phase-Neutral voltage
L1
1
L2
9
L3
17
III
31
Phase-Phase voltage
L12
28
L23
29
L31
30
III
32
Current
L1
2
L2
10
L3
18
III
33
Frequency
-
27
-
-
-
-
-
-
Total Active Power
L1
3
L2
11
L3
19
III
34
Consumed Active Power
L1
700
L2
707
L3
714
III
721
Generated Active Power
L1
728
L2
735
L3
742
III
749
Total Apparent Power
L1
6
L2
14
L3
22
III
37
Consumed Apparent Power
L1
704
L2
711
L3
718
III
725
Generated Apparent Power
L1
732
L2
739
L3
746
III
753
Total Reactive Power
L1
69
L2
70
L3
71
III
72
Total Consumed Reactive Power
L1
703
L2
710
L3
717
III
724
Total Generated Reactive Power
L1
731
L2
738
L3
745
III
752
Total Inductive Reactive Power
L1
4
L2
12
L3
20
III
35
Consumed Inductive Reactive Power
L1
701
L2
708
L3
715
III
722
Generated Inductive Reactive Power
L1
729
L2
736
L3
743
III
750
Total Capacitive Reactive Power
L1
5
L2
13
L3
21
III
36
Consumed Capacitive Reactive
Power
L1
702
L2
709
L3
716
III
723
Generated Capacitive Reactive Power
L1
730
L2
737
L3
744
III
751
Total Power Factor
L1
7
L2
15
L3
23
III
38
Generated Power Factor
L1
705
L2
712
L3
719
III
726
Consumed Power Factor
L1
733
L2
740
L3
747
III
754
Cos
φ
Total
L1
8
L2
16
L3
24
III
39
Cos
φ
Generated
L1
706
L2
713
L3
720
III
727
Cos
φ
Consumed
L1
734
L2
741
L3
748
III
755
THD% Voltage
(3)
L1
40
L2
41
L3
42
-
-
THD % Current
(3)
L1
44
L2
45
L3
46
-
-
Quality Parameter
(2) (3)
L1
109
L2
110
L3
111
III
112
(2)
The output is activated when any of the quality parameters (overvoltage, gap or interruption) meet the programmed
parameters.
(3)
These variables are not present when programming the Analogue Output variables.
The outputs are also configurable depending on the digital or analogue inputs of the connected ex-
pansion modules (
Note:
SLOT1 is the expansion module nearest
line-CVM
, SLOT2 is the following expansion module.
The code
MANUAL
(4)
is used to manually activate the output, see
Содержание line-LM20I-TCP kit
Страница 1: ...INSTRUCTION MANUAL Expansion modules for the line CVM and line EDS devices M239B01 03 20B...
Страница 2: ...2 line M Instruction Manual...
Страница 95: ...95 Instruction Manual line M 118 105 45 35 7 90 44 70 Figure 47 line LM20I TCP kit dimensions...
Страница 103: ...103 Instruction Manual line M 118 157 5 45 35 7 90 44 70 Figure 52 line LM40I TCP kit dimensions...
Страница 105: ...105 Instruction Manual line M 16 CE CERTIFICATE...
Страница 106: ...106 line M Instruction Manual...
Страница 107: ...107 Instruction Manual line M...