Page 24 of 26
PARAMETER
SYMBOL
Instant
Maximum Minimum
Units
Active power III
kW III
1E-1F
7E-7F
DE-DF
w
Inductive power III
KvarL III
20-21
80-81
E0-E1
w
Capacitive power III
KvarC III
22-23
82-83
E2-E3
w
Cos
φ
III
Cos
φ
III
24-25
84-85
E4-E5
x 100
Power factor III
PF III
26-27
86-87
E6-E7
x 100
Frequency
Hz
28-29
88-89
E8-E9
Hz x 10
Voltage line L1-L2
V12
2A-2B
8A-8B
EA-EB
V x10
Voltage line L2-L3
V23
2C-2D
8C-8D
EC-ED
V x10
Voltage line L3-L1
V31
2E-2F
8E-8F
EE-EF
V x10
% THD V L1
%THD VL1
30-31
90-91
F0-F1
% x 10
% THD V L2
%THD VL2
32-33
92-93
F2-F3
% x 10
% THD V L3
%THD VL3
34-35
94-95
F4-F5
% x 10
% THD A L1
%THD AL1
36-37
96-97
F6-F7
% x 10
% THD A L2
%THD AL2
38-39
98-98
F8-F9
% x 10
% THD A L3
%THD AL3
3A-3B
9A-9B
FA-FB
% x 10
Apparent power III
KvaIII
42-43
A2-A3
102-103
w
Maximum demand
Md (Pd)
44-45
A4-A5
104-105
w/VA/mA
Three-phase current (
average
)
A_AVG
46-47
A6-A7
106-107
mA
Neutral current
In
48-49
A8-A9
108-109
mA
Maximum demand A2
Md (Pd)
52-53
B2-B3
112-113
mA
Maximum demand A3
Md (Pd)
54-55
B4-B5
114-115
mA
PARAMETER
SYMBOL
Instant
Units
Active energy
kW·h III
3C-3D
w·h
Inductive reactive energy
kvarL·h III
3E-3F
w·h
Capacitive reactive energy
kvarC·h III
40-41
w·h
Apparent energy
kVA·h III
56-57
w·h
Active energy generated
kW·h III (-)
58-59
w·h
Inductive energy generated
kvarL·h III (-)
5A-5B
w·h
Capacitive energy generated
kvarC·h III (-)
5C-5D
w·h
Apparent energy generated
kVA·h III (-)
5E-5F
w·h