4�6�4� SECONDARY CURRENT
(
ONLY THE MODEL
CVM-C5-ITF-485
)
Onthisscreenthecurrenttransformersecondaryisselected�
Usethe
keytojumpbetweenthetwopossibleoptionsfor
thecurrenttransformersecondary(1Aor5A)�
Tovalidatetheinformationandgotothenextprogrammingstep,press
�
Note:
Ifthevoltageratiotogetherwiththeprogrammedcurrentratioexceedsthemaximum
powervaluethatcanbemeasuredbythedevice,itwillreturntotheprimaryvoltage
programmingstepwhenyoupressthe
key�
Nota :
To apply the change to the second current transformer is necessary to reset the computer.
4�6�5� MEASUREMENT SYSTEM
Onthisscreenthemeasurementsystemtobeusedinthe
installationisselected�
The
keyjumpsbetweenthedifferentoptions
Three-phasenetworkmeasuringwitha4-wireconnection�
Three-phasenetworkmeasuringwitha3-wireconnection�
Three-phasenetworkmeasuringwitha3-wireconnectionandtransformersinan
ARONconnection
�
Two-phasenetworkmeasuringwitha3-wireconnection�
Phase-to-phasesingle-phasenetworkmeasuringwitha2-wireconnection�
Phase-to-neutralsingle-phasenetworkmeasuringwitha2-wireconnection�
Tovalidatetheinformationandgotothenextprogrammingstep,press
�
30
CVM-C5-xxx-485
Instruction Manual