----- Supply network analyzer CVM 96 Ethernet -------- ----- Page No. 44
12.- APPENDIX C: Ethernet communication.
Description of System Protocol and communications.
The CVM96-Ethernet analyzer has been designed specially to communicate in
Ethernet networks. Thanks to this communication system the wiring used in the
RS485 network can be exceptionally optimized, improving this way the existing
networks, and making very easy the installation procedure.
The device is delivered with two diskettes which contain the following components:
•
Extras: configuration program to set the communication parameters and also
some utilities; technical manual of the analyzer.
•
Com Redirector: program to configure the *virtual ports.
The CVM96-Ethernet analyzer has an RJ45 Ethernet 10Base-T/100Base-TX
connector (autodetect), which will connect the analyzer to the Ethernet network (hub
or switch), or using a direct wire (crossed connection) to the master computer that
holds the software application.
The connection with the master computer will be made by means of shielded twisted
pair wires (suitable for Ethernet networks). One side of the wire will be
connected to the CVM96-Ethernet and the other one to the hub or
switch existing in the Ethernet network.
In case we need a direct connection to a computer or any device with an
Ethernet input, the wires must have a suitable configuration according to type of
communication.
1-Orange
-- 1-Orange
1-Orange
-- 1-Green
2-Orange/White
-- 2-Orange/White
2-Orange/White
-- 2-Green/White
3-Green
-- 3-Green
3-Green
-- 3-Orange
4-Blue
-- 4-Blue
4-Blue
-- 4-Blue
5-Blue/White
-- 5-Blue/White
5-Blue/White
-- 5-Blue/White
6-Gree/White
-- 6-Gree/White
6-Green/White
-- 6-Orange/White
7-Brown
-- 7-Brown
7-Brown
-- 7-Brown
8-Brown/White
-- 8-Brown/White
8-Brown/White
-- 8-Brown/White
STANDARD ETHERNET CABLING
DIRECT ETHERNET CABLING