Application notes
CDP
2�- KOSTAL PIKO INVERTER
The
CDP
and the inverter communicate via an RS-485 bus. This RS-485 bus can connect up
to 32 inverters, although the number of inverters in the vast majority of domestic installations
ranges from 1 to 3.
2.1.- COMMUNICATION CABLE
To communicate with a
KOSTAL PIKO
inverter using a
CDP
, the inverter must be equipped
with a communications card with an RS-485 interface (
).
Figure 1:Communication card.
Table 3:Communication card.
No
Description
1
Connection terminal S0/AL-Out (2-pole)
2
2 Ethernet connections (RJ45)
3
Analog interface connection terminal
4
Connection terminal for RS-485 interface
5
Extension module connection terminal
The connector is a terminal for a 0.25mm
2
cable
Functions of the communication cable terminals between the
CDP
and the inverter:
Table 4:
Functions of the communication cable terminals
.
CDP
R2 channel communications
connector
Communication card
RS-485 Terminal (No. 4)
Terminal
Description
Terminal
Description
1
A+
A+
RS-485 A +
3
B-
B-
RS-485 B -
5
GND
GND
GND
It is not necessary to wire the GND terminal, although it is advisable to do so for long distances.