183
Instruction Manual
AFQm
ENGLISH
The phase balancing option in
AFQm-3WF-xxxx
works in unbalances produced by loads
connected between phases in three-phase mains without neutral. The
AFQm-3WF-xxxx
does not compensate unbalances produced by single-phase loads connected between
phase and neutral. Use a
AFQm-4WF-xxxx
to correct this type of unbalances.
Priority
Enable this option so that the device prioritises the functions in case of filter current saturation due to
overload:
With the function
enabled
, the current balancing between phases and the reactive current compensa-
tion is prioritised over the harmonic filtering.
With the function
disabled
, priority is given to the current harmonic filtering and power factor correc-
tion and overload balancing are penalised.
Table 24: Order of priorities
Priority
Order of priorities function
Disabled
Enabled
+
Harmonic filtering
Phase balancing
Power factor correction
-
Phase balancing
Power factor correction
Harmonic filtering
Reactive
Enable this function so that the device compensates the reactive energy or corrects the displacement
power factor, cos
Φ
.
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration values
Содержание AFQm
Страница 2: ...2 AFQm...
Страница 3: ...3 AFQm CONTENIDO CONTENTS MANUAL DE INSTRUCCIONES 4 INSTRUCTION MANUAL 117...
Страница 112: ...112 AFQm Manual de Instrucciones ESPA OL 608 812 1755 665 465 1890 Figura 108 Dimensiones AFQm tipo armario...
Страница 114: ...114 AFQm Manual de Instrucciones ESPA OL 14 CERTIFICADO CE...
Страница 115: ...115 Manual de Instrucciones AFQm ESPA OL...
Страница 116: ...116 AFQm Manual de Instrucciones ESPA OL...
Страница 225: ...225 Instruction Manual AFQm ENGLISH 608 812 1755 665 465 1890 Figure 107 Dimensions Cabinet type AFQm...
Страница 227: ...227 Instruction Manual AFQm ENGLISH 14 CE CERTIFICATE...
Страница 228: ...228 AFQm Instruction Manual ENGLISH...
Страница 229: ...229 Instruction Manual AFQm ENGLISH...