2 - Case of a Master unit with several slaves: 

 

- 1 master must be associated with 1 slave only

 

- This must therefore be repeated as many times as there are slaves

 

- Perform the same operation as in

 paragraph 1 with the first slave.

 

- Do the same operation as in paragraph 1 with all other slaves associated with this mastere.

 

- Starting from the 2nd slave configuration lasts 30 seconds to 1 minute

Note:

 Allow a maximum of 15 slaves for 1 master unit.

3 - Verify configuration via diagnostics d01 and d02

 

- d01 relates to the master

 

- d01 gives the address of the master on the bus, for instance: 1

 

- d02 relates to the slave

 

- d02 enables you to check which master is associated with the queried slave. All slaves with their d02 at 1 are associated 

with master no.1.

Deconfiguring a Master/Slave loop 

 a) 

Start with the slave

 

- To switch to configurator mode, press buttons 

 

 for 5 seconds.

 

- Press 

 for 5 seconds until the display "dEL" flashes.

 b) 

Go on to the master

 

- Perform the same operation as above

  c)  Configuration takes between 30 seconds and 1 min (approximately). It is completely finished when "dEL 

0

" goes back to 

being fixed.

  d) To return to normal display, press

 

 

  e) If the display "Err" appears, an error has occurred

Check: 

 

- The bus wiring

 

- Its power supply

 

- Parameter P00 on the master and slave

and restart the operation

Configuration

on SLAVE

on MASTER

Step 1

- Access the "CnF" menu on the Slave

 / 

 for 5 s

witch the Slave to deconfiguration

 for 5 s 

- "dEL" flashes

Step 2

- Access the "CnF" menu on the Master

 / 

 for 5 s

Switch the Master to deconfiguration

 for 5 s 

- "dEL" flashes

Step 3

Wait 30 s to 1 min

"dEL 

6

"

flashes 

"dEL 

4

"

flashes 

Step 4

End of deconfiguration if:

"dEL 

0

"

Fixed display

"dEL 

0

"

Fixed display

Step 5

Deconfiguration successful

Button 

 to exit CnF menu

EN

 

 

EN - 15 EN7515935-00

Содержание V3000 KNX

Страница 1: ...V3000 KNX 03 2017 EN7515935 00 C o n t r o l m a n u a l...

Страница 2: ......

Страница 3: ...IC 6 6 AIR TEMPERATURE MEASUREMENT 10 7 SPECIFICATIONS OF SENSORS USED BY THE V3000 10 8 WATER TEMPERATURE MEASUREMENT 10 9 CONTROL ALGORITHM 11 10 CONNECTING THE FRAME CONTACT 12 11 FRESH AIR 13 12 M...

Страница 4: ...etpoint and also access the set up and diagnostic values Standby button This enables you to change the operating mode comfort standby economy frost protection according to the chosen set up Ventilatio...

Страница 5: ...up Ventilation 1 2 or 3 ventilation symbols displayed simultaneously to indicate LS MS or HS If auto is selected the AUTO symbol appears in addition to the ventilation symbols If AUTO selected the LE...

Страница 6: ...increments of 0 5 19 0 P03 Cooling comfort setpoint Setpoint for cooling control in comfort mode 5 40 increments of 0 5 26 0 P04 Heating Standby setpoint Setpoint for heating control in Standby mode...

Страница 7: ...ically restarted 0 1 2 3 0 P47 Operating mode activated by standby button on user terminal 1 Comfort Frost protection 2 Comfort Eco 3 Comfort Standby 1 2 3 1 P48 Comfort override delay Override to rem...

Страница 8: ...of 5 75 P59 Hot water coil nominal capacity Nominal capacity in kW of the hot water coil rounded up to the nearest 100W Used for certain energy consuming applications 0 99 0 resolution of 0 1 100 P60...

Страница 9: ...17 Heating heat consumption Calculated heat consumption of heating coil display unit hundred kWh d18 Air conditioning heat consumption Calculated heat consumption of air conditioning coil display unit...

Страница 10: ...versa If the controller has just been supplied wait for system initiation 6 mins Check the electrical connection of the valves refer to wiring diagram No heating Check that The hot setpoint T C is gre...

Страница 11: ...condensates on the cooling coil This alarm is present as long as there is condensation present on the cooling coil Check the water temperature E15 Slave cut off from master No dialogue between a mast...

Страница 12: ...bypass often called a 4 way valve Sensor Changeover operating algorithm If the changeover sensor measures water temperature greater than 7 C adjustable in P27 at ambient temperature the water is deeme...

Страница 13: ...P48 24 5 the setpoint overrides are stored in all operating scenarios The current fan speed is not memorized and returns to AUTO Operating mode activated by standby button According to parameter P47 p...

Страница 14: ...2 Presence contact comfort Eco local override impossible 3 Presence contact comfort Standby local override impossible 4 Condensate pump alarm fan coil unit switched off and cold valve closed 5 Fan un...

Страница 15: ...y mechanism being triggered 11 FRESH AIR Parameters P00 and configuration procedure Diagnostic d01 and d02 The V3000 may perform the master slave function via 3 different ways Master slave by hot cold...

Страница 16: ...n to 1 5 mins It is completely finished when the fixed display Add 0 appears d To return to normal display press e If the display Err appears an error has occurred Check The bus wiring Its supply Para...

Страница 17: ...ave loop a Start with the slave To switch to configurator mode press buttons for 5 seconds Press for 5 seconds until the display dEL flashes b Go on to the master Perform the same operation as above c...

Страница 18: ...elow Switch the radio receiver to configuration mode pressing its button for 3 seconds until the green LED starts flashing more slowly On the remote control Remove the insulation tab on the batteries...

Страница 19: ...up to 8 terminal units with a single remote control each terminal unit must be equipped with a radio frequency receiver To configure Set P00 to 0 on all the controllers in the master slave loop defaul...

Страница 20: ...a Blank terminal b Wall mounted dial terminal 14 TECHNICAL SPECIFICATIONS EN7515935 00 EN 18...

Страница 21: ...c Display terminal d Radio frequency receiver EN EN 19 EN7515935 00...

Страница 22: ...the room the connection to the controller is provided by means of flexible wires with a maximum length of 30 m and section 1 mm 2 conductors see terminal 1 and 2 of the regulator It is essential to u...

Страница 23: ......

Страница 24: ...in mind CIAT reserves the right without notice to proceed with any technical modification Si ge social Avenue Jean Falconnier B P 14 01350 Culoz France Tel 33 0 4 79 42 42 42 Fax 33 0 4 79 42 42 10 i...

Отзывы: