CIAT V3000 KNX Скачать руководство пользователя страница 12

 

Parameter P24

Diagnostics d08, d09

The V3000 offers the possibility of controlling the air temperature via a return sensor or an indoor environment sensor (P24).

If you can choose between the two, it is preferable to opt for the indoor environment sensor, since it provides a better picture of 

the room temperature.

The indoor environment sensor is situated inside the user terminal unit. When it is used, particular care must be taken in choosing 

the location of the user terminal in the room (do not expose it to sunlight, or place it on top of a device giving off heat - put it on 

an inside partition).
The end of the wiring conduit must be heat insulated.

20 cm

mini

150 cm

~ 150 cm

The choice of sensor is made using parameter P24 (=0: return sensor; =1: indoor environment sensor).

If the selected sensor is faulty, the other sensor immediately takes over. A symbol 

 is displayed on the screen and the fault can 

also be looked up in the variable of diagnostic d22.

In case of doubt about the origin of the displayed temperature value, the value measured by the return sensor can be read in d09. 

The value measured by the indoor environment sensor can be read in d08. If the sensor is absent, the value displayed is equal to 0.0°C.

The sensor measurement can be corrected by means of parameter P25 (return sensor) or P26 (indoor environment sensor).

6 - AIR TEMPERATURE MEASUREMENT

 

Parameters P27, P28

Diagnostic d11, d12

The 2-pipe hot/cold fan-coil units may be fitted with a water temperature sensor (or changeover sensor). It must be positioned 

using a conduit clip by the installer upline of the four-way valve (water piping end). It is fastened to the pipe by means of 

electrician's clamps.

Position and use of the changeover sensor

Water inlet 

pipe

Insulation

Clamp

Sensor adapter

Sensor

Valve motor

3-way valve with  

built-in bypass  

(often called a  

4-way valve)

Sensor

 

Changeover operating algorithm:

 

-  If the changeover sensor measures water temperature greater than 7°C (adjustable in P27) at ambient temperature, the 

water is deemed to be hot.

 

- If the changeover sensor measures water temperature less than 4°C (adjustable in P28) at ambient temperature, the water 

is deemed to be cold.

 

- If the changeover sensor measures water temperature between these 2 values, the water is deemed neutral.

 

Changeover operation with water at neutral temperature:

In this scenario, and when there is an established need from the controller, the V3000 launches a test cycle on the valve every 45 

mins so as to check the network's available water temperature (valve 100 % opened to authorise water circulation in the terminal 

unit coil).

 

- If this temperature does not vary, the V3000 keeps the same status

 

- If this temperature varies and returns to the conditions described above, the V3000 re-authorises its control cycle

Important

:

 the changeover sensor measures the surface temperature of the piping. There is an obvious difference between the 

actual water temperature and the surface temperature. The water speed will therefore be selected so as to guarantee changeover 

switching.

-  For P31 = 1, if nothing is connected between terminals S2 and C, the controller deduces that the water circulating in the coil is 

still cold. If there is a bridge between these terminals, the controller deduces that the water is still hot.

-  For P31 = 2, the controller waits to receive the water temperature from the central management unit before starting in heating or 

cooling mode (if it does not receive a temperature value, it will not start its heating or cooling control sequence and will indicate 

alarm E11)

7 - SPECIFICATIONS OF SENSORS USED BY THE V3000

All the sensors used by the V3000 (return, changeover) have the same specifications

Temperature

°C

5

10

15

20

25

30

35

Resistance

Ohms

22 050

17 960

14 690

12 090

10 000

8 313

6 940

8 - WATER TEMPERATURE MEASUREMENT

  EN7515935-00 

 EN - 10 

Содержание V3000 KNX

Страница 1: ...V3000 KNX 03 2017 EN7515935 00 C o n t r o l m a n u a l...

Страница 2: ......

Страница 3: ...IC 6 6 AIR TEMPERATURE MEASUREMENT 10 7 SPECIFICATIONS OF SENSORS USED BY THE V3000 10 8 WATER TEMPERATURE MEASUREMENT 10 9 CONTROL ALGORITHM 11 10 CONNECTING THE FRAME CONTACT 12 11 FRESH AIR 13 12 M...

Страница 4: ...etpoint and also access the set up and diagnostic values Standby button This enables you to change the operating mode comfort standby economy frost protection according to the chosen set up Ventilatio...

Страница 5: ...up Ventilation 1 2 or 3 ventilation symbols displayed simultaneously to indicate LS MS or HS If auto is selected the AUTO symbol appears in addition to the ventilation symbols If AUTO selected the LE...

Страница 6: ...increments of 0 5 19 0 P03 Cooling comfort setpoint Setpoint for cooling control in comfort mode 5 40 increments of 0 5 26 0 P04 Heating Standby setpoint Setpoint for heating control in Standby mode...

Страница 7: ...ically restarted 0 1 2 3 0 P47 Operating mode activated by standby button on user terminal 1 Comfort Frost protection 2 Comfort Eco 3 Comfort Standby 1 2 3 1 P48 Comfort override delay Override to rem...

Страница 8: ...of 5 75 P59 Hot water coil nominal capacity Nominal capacity in kW of the hot water coil rounded up to the nearest 100W Used for certain energy consuming applications 0 99 0 resolution of 0 1 100 P60...

Страница 9: ...17 Heating heat consumption Calculated heat consumption of heating coil display unit hundred kWh d18 Air conditioning heat consumption Calculated heat consumption of air conditioning coil display unit...

Страница 10: ...versa If the controller has just been supplied wait for system initiation 6 mins Check the electrical connection of the valves refer to wiring diagram No heating Check that The hot setpoint T C is gre...

Страница 11: ...condensates on the cooling coil This alarm is present as long as there is condensation present on the cooling coil Check the water temperature E15 Slave cut off from master No dialogue between a mast...

Страница 12: ...bypass often called a 4 way valve Sensor Changeover operating algorithm If the changeover sensor measures water temperature greater than 7 C adjustable in P27 at ambient temperature the water is deeme...

Страница 13: ...P48 24 5 the setpoint overrides are stored in all operating scenarios The current fan speed is not memorized and returns to AUTO Operating mode activated by standby button According to parameter P47 p...

Страница 14: ...2 Presence contact comfort Eco local override impossible 3 Presence contact comfort Standby local override impossible 4 Condensate pump alarm fan coil unit switched off and cold valve closed 5 Fan un...

Страница 15: ...y mechanism being triggered 11 FRESH AIR Parameters P00 and configuration procedure Diagnostic d01 and d02 The V3000 may perform the master slave function via 3 different ways Master slave by hot cold...

Страница 16: ...n to 1 5 mins It is completely finished when the fixed display Add 0 appears d To return to normal display press e If the display Err appears an error has occurred Check The bus wiring Its supply Para...

Страница 17: ...ave loop a Start with the slave To switch to configurator mode press buttons for 5 seconds Press for 5 seconds until the display dEL flashes b Go on to the master Perform the same operation as above c...

Страница 18: ...elow Switch the radio receiver to configuration mode pressing its button for 3 seconds until the green LED starts flashing more slowly On the remote control Remove the insulation tab on the batteries...

Страница 19: ...up to 8 terminal units with a single remote control each terminal unit must be equipped with a radio frequency receiver To configure Set P00 to 0 on all the controllers in the master slave loop defaul...

Страница 20: ...a Blank terminal b Wall mounted dial terminal 14 TECHNICAL SPECIFICATIONS EN7515935 00 EN 18...

Страница 21: ...c Display terminal d Radio frequency receiver EN EN 19 EN7515935 00...

Страница 22: ...the room the connection to the controller is provided by means of flexible wires with a maximum length of 30 m and section 1 mm 2 conductors see terminal 1 and 2 of the regulator It is essential to u...

Страница 23: ......

Страница 24: ...in mind CIAT reserves the right without notice to proceed with any technical modification Si ge social Avenue Jean Falconnier B P 14 01350 Culoz France Tel 33 0 4 79 42 42 42 Fax 33 0 4 79 42 42 10 i...

Отзывы: