EN
For CW 115 size filters
-
Unscrew the clamps on the bottom of the filter (detail A)
-
Release the filter by pulling up the tab on the top of the filter (detail B)
Replace the used filters by new filters. Take care to note the direction of air flow indicated on the new filters.
Always make sure that the filter elements are properly positioned before compressing them or switching the unit back on
Detail A
Detail B
13.2 - Cooling coil
Maintenance intervals
As the cooling coil is protected by a filter, its air circuits require very little maintenance
Always cut the power supply to the cabinet before proceeding with cleaning.
Electric heater
Maintenance intervals
The electric heater requires very little maintenance. However, the following checks are necessary:
Visually inspect the heating elements, wires and connection cables after every 1500 hours of operation.
Check and retighten the connections once or twice a year.
Sizes CW 40 to 100
Size CW115
Electric heater
Side door
1
B
To remove the heaters
-
Unscrew the bolt and remove the washer, and push the pin backwards to release it from its housing. Carry out this procedure
in reverse when refitting.
The electric heater is located behind the exchanger (chilled water coil).
Open the side door to access it. Clean using an air nozzle.
13 - MAINTENANCE
EN-63 MAGISTER
®