Units
CW 40
CW 53
CW 78
CW 100
CW115
Air flow (m
3
/h)
13 300
13 300
20 500
27 000
27 500
* Maximum operating pressure with G4 / COARSE filtration: 65 %
175
237
400
124
400
* Maximum operating pressure with F7 / ePM1 filtration: 55 %
66
148
400
30
395
Total/sensible cooling capacity (kW)
46 / 46
51/ 51
78 / 78
100 / 100
124 / 124
Water flow (m
3
/h)
7,9
8,8
13
17
21
"Pressure drop (mWC) (Coil + valve)"
7,5
7,7
7,5
6,2
10
* Conditions: return air 26 °C 40 % (RH)
Water temperature 10/15 °C* Maximum operating pressure dependent on air flow rate. Take off approximately 20 Pa if there is a hot water coil on the MAGISTER
®
.
The operation point can be adjusted directly via the controller. All air flow/operating pressure combinations are therefore possible with
maximum values as per the values in the table above.
Units
CW40
CW53
CW78
CW100
CW115
Air flow (m
3
/h)
13 300
13 300
20 500
27 000
27 500
* Maximum operating pressure with G4 / COARSE filtration: 65 %
174
236
400
123
400
* Maximum operating pressure with F7 / ePM1 filtration: 55 %
67
145
400
30
384
Total/sensible cooling capacity (kW)
56 / 56
60/ 60
94 / 94
132 / 132
124 /124
Water flow (m
3
/h)
9,6
10
16
23
21
"Pressure drop (mWC) (Coil + valve)"
10
10
10
10
10
* Conditions: return air 32 °C 35 % (RH)
Water temperature 12/17 °C* Maximum operating pressure dependent on air flow rate. Take off approximately 20 Pa if there is a hot water coil on the MAGISTER
®
.
The operation point can be adjusted directly via the controller. All air flow/operating pressure combinations are therefore possible with
maximum values as per the values in the table above.
Maximum permitted differential pressure on cold water valve
CW40
CW53
CW78
CW100
CW115
KV
16
16
25
40
25
∆
P max. Three-way valve
300
300
300
260
300
∆
P max. Two-way valve
1200
1200
1000
260
1000
11.1.4 - Filter
Filters:
EN 779-2012 efficiency: G4
ISO16890 efficiency: COARSE 65%
Thickness: 48 mm
Efficiency: 90% gravimetric
Filter area: 2 x the face area
Fire rating: M1
Filters:
EN 779-2012 efficiency: F7
ISO16890 efficiency: ePM1: 55%
Thickness: 48 mm
Efficiency: 85% opacimetric
Filter area: 17 x the face area
Fire rating: M1
CHILLED WATER
CW 40
CW 53
CW 78
CW 100
CW115
Dimensions
1192x600
1192x600
1192x600
1192x600
1140x450
1192x360
1192x360
Quantity
1
1
3
4
6
1
2
Thickness G4/COARSE: 65 % (mm)
48
48
48
48
48
Thickness F7/ePM1: 55 % (mm)
48
48
48
48
48
11 - TECHNICAL CHARACTERISTICS
MAGISTER
®
EN-50