2 - THE CONTROL PLC
2.1 - Introduction
The control PLC is used to control and monitor the operating status of the various components of the air handling unit. Depending
on the options, it provides temperature control and fan management. It can be connected to a CMS so that it can be controlled
remotely.
2.2 - Inputs/outputs
The PLC has analogue and on/off inputs/outputs. The list of inputs/outputs is described below (according to the options installed).
The PLC is installed in the main electrics box and the expansion modules (if present) are in the additional boxes installed as close
as possible to the elements being controlled.
Input/output designations
Type
U
On/off or analogue input
GND, C
Shared
DI
On/off input
Y
Analogue output
Out
Polarised 24 V on/off output
NO
Normally open potential-free on/off output
NC
Normally closed potential-free on/off output
Connector
Inputs
Type
Description
J1
G
+24 Vac power supply
G0
Shared
J2
U1
0-10V
CO
2
air quality measurement or supply air duct pressure sensor
U2
NTC
Return air temperature sensor
U3
NTC
Supply air temperature sensor
GND
Shared
J3
U4
NTC
Fresh air temperature sensor
U5
ON/OFF
Changeover thermostat
+Vdc
Not used
+5VR
Not used
GND
Shared
J4
U6
ON/OFF
Intake filter pressure switch
U7
ON/OFF
Exhaust filter pressure switch
+Vdc
Not used
+5VR
Not used
GND
Not used
J5
U8
ON/OFF
DX unit defrosting
U9
0 - 5V
Air intake fan differential pressure sensor (controller software version >= V09)
otherwise: not used
U10
0 - 5V
Extraction fan differential pressure sensor (controller software version >= V09)
otherwise: not used
+Vdc
Not used
+5VR
Not used
GND
Shared
EN-5
FLOWAY ACCESS