EN
EN - 13
DIMENSION OF THE REFRIGERANT CIRCUITS (Indoor DX coil)
The diameter of the condensate tube on all the pans is 16 mm
2 row coil
Sizes
1000
2000
3000
5000
7500
Connection Ø
Refrigerating
Liquid inlet
12 mm
12 mm
16 mm
16 mm
2x16 mm
Gas outlet
16 mm
18 mm
22 mm
28 mm
2x22 mm
Internal volume (litres)
0.465
0.952
1.49
2.16
3.63
3-4 row coil
Sizes
1000
2000
3000
5000
7500
Connection Ø
Refrigerating
Liquid inlet
12 mm
12 mm
16 mm
2x22 mm
2x22 mm
Gas outlet
16 mm
18 mm
28 mm
2x28 mm
2x28 mm
Internal volume (litres)
0.932
1.91
2.98
4.32
5.24
ELECTRICAL CONNECTIONS
Sizes
1000
2000
3000
5000
7500
Voltage (V)
230 V 1-Ph
400 V 3-Ph
Max. current (A) without electric heater
5.4
3.6
6.1
8.8
10.3
Minimum power supply cable section without
electric heater
3G1
4G0.75
4G1
4G1.5
4G1.5
Max. current (A) with indoor electric heater
32.4
21.8
33.5
50.6
59.4
Minimum power supply cable section with electric
heater
3G6
4G2.5
4G6
4G10
4G10
Disconnect switch size
OT40 (40 A)
OT63 (63 A)
Max. terminal section (mm
2
)
0.75 to 10
1.5 to 35
Torque Value (N.m)
0.8
2
• Connect the unit's electrics to the power network as per the table above.
• Connection to the machine's general disconnect switch located inside it (Ø 22.2 blanking cover provided).
• For sections between 0.75 and 2.5 mm2, a H 05 VV-F type cable may be used, otherwise the cable must be type H 07 RN-F.
• The power supply cable must be sized in accordance with current standards and regulations.
• The supply cable must be secured using the anchorage provided (located between the disconnect switch and the Ø 22.2
blanking cover). Once the supply cable has been fed through and connect, tighten the clamp fully and cut the end extending
past the clamp.
• Respect the current assigned to the disconnect switch for the air handling unit.
• The leakage current may reach 13 mA. Earthing is essential. Each unit is equipped with 2 earth terminals (PE) indicated by
the logo
, one close to the disconnect switch, and the other on one of the unit's feet. Both terminals must be permanently
connected.
Ø 22.2 blanking cover
Anchorage
Earth terminals
Disconnect
switch