2.5 Hydraulic connections
2.5.1 Pipeline diameter
The minimum internal diameter that must be respected for the pipelines of the hydraulic connections varies according to the model:
2.5.2 Connections
The choice and sizing of the hydraulic lines must be made by an expert who must operate according to the rules of good practice
and the laws in force.
To make the connections:
- position the hydraulic lines
- assemble the adaptor connections provided if necessary (fig. 10 ref. A)
- tighten the connections using the “spanner and counter spanner” method (fig. 10 ref. B)
- check for any leaks of liquid
- coat the connections with insulating material.
The hydraulic lines and connections must be thermally insulated.
Avoid partially insulating the pipes.
Do not over-tighten to avoid damaging the insulation.
Use hemp and green paste to seal the threaded connections; the use of Teflon is advised when there is anti-freeze in the
hydraulic circuit.
2.6 Condensation discharge
The condensation discharge network must be suitably sized (minimum inside pipe diameter 16 mm) and the pipeline positioned
so that it keeps a constant inclination, never less than 1%. The draining tube is connected to the drain base, placed at the bottom
on the side frame under the hydraulic outlets.
- If possible, drain the condensates directly into a gutter.
- When discharging directly into the main drains, it is advisable to make a siphon to prevent bad smells returning up the pipe
towards the room. The curve of the siphon must be lower than the condensation collection bowl.
- If the condensation needs to be discharged into a container, it must be open to the atmosphere and the tube must not be
immerged in water to avoid problems of adhesiveness and counter-pressure that would interfere with the normal outflow.
- If a difference in level prevents the draining of condensates, a pump (not provided) must be assembled under the side drain pan
In any case, consult the specific instructions in the condensation discharge pump kit (not provided).
After the installation, check the condensates drain correctly by slowly pouring about 1/2 l water into the
condensates drain pan for 5-10 minutes
2.6.1 Fitting the condensation discharge device.
Connect to the condensation collection tray discharge union (fig. 11 ref. A) a pipe for the outflow of the liquid (fig. 11 ref. B)
blocking it adequately. Check that the drip-collector extension (fig. 11 ref. C) is present and correctly installed.
A
B
Fig. 10
C
A
B
Fig. 11
Divio 700
Ø12 mm
Divio 900
Ø14 mm