7 - WATER CONNECTIONS
7.1 - Connection to be tightened (HELIOTHERME LP Water)
The side of the HELIOTHERME hydraulic connection may also be positioned to the left or right of the air flow direction simply by
turning it (for HEATING applications). Ensure that the cable glands on the motor terminal box are facing downwards to ensure the
assembly is correctly sealed.
The hydraulic connection on the HELIOTHERME LP water version is screwed in using threaded unions. The coil supply pipes and
the general supply pipes must be connected and tightened according to good working practice, namely, using two adjustable
wrenches to avoid any torsion of the coil collector.
CIAT shall in no way be held liable for damage to the coil if these installation instructions are not followed and the warranty shall
be invalidated.
Two keys are used to ensure the counter
torque; the HELIO connection tube will not be
pierced.
If only one key is used, the connection tube may
twist and be pierced.
This is not covered by the CIAT warranty
7.2 -
Connection to be welded (Heliotherme HP fluid)
Ensure that the casing and the rubber caps are protected from the excessive heat produced during welding by using a damp cloth
when welding between the HELIOTHERME and the supply pipes.
Welding must be carried out according to good working practice, especially on the filler metal.
7.3 - Condensate drain connection (HELIOTHERME used for cooling or reversible purposes)
For COOLING applications, the condensate drain pan is integrated into the HELIOTHERME. This is of antibacterial design thanks
to its diamond pointed based.
M5 CBLX screw
Lower groove
2nd
gasket
1st
gasket
Upper groove
Condensate
drain pipe
Procedure for fitting the union on the pan:
1. Position the 1st gasket into the lower groove on the union
2. Position the 2nd gasket into the upper groove on the union
3. Fix the assembly onto the condensate drain pan using the M5
CBLX screw supplied in the threaded insert fixed onto the pan.
Condensate drain pan connection
Once the union is fitted with these gaskets, fit the pipe onto the
union (outer diameter 32 mm). The gaskets provide an adequate
seal for the union.
Nevertheless, it is important to ensure that this connection
between the union and the pipe does not bear all the weight of
the drain column fitted with a siphon which must be installed
according to good working practice (risk of detachment).
EN-11
H4000 HELIOTHERME