NA 03.28 D
EN - 8
3.3 Filtration
- G2 filters: the cell may be inserted in any direction regardless of the direction of air flow,
- G4 filters: the mesh holding the medium in place must face the discharge air side,
- HPS bag filters HPS (F6, F7, F8), high-efficiency and HPR filters: the cells on the frame side must face the incoming air,
- HEPA filters (H10, H14): refer to the instructions supplied with filters for information on fitting and maintaining them,
- Carbon filters: refer to the instructions supplied with the filters.
G2 and G4 filters are supplied fitted on the unit. Other filters are supplied in their packing.
G4 filter
HPS filter
HPR or carbon filter
HEPA filter
3.4 Water and direct expansion coil
Do not remove the protective caps until you are ready to connect the coils.
Coil with water supply
Always use two spanners when connecting or tightening the hydraulic couplings to avoid twisting the pipes and applying stress on
the welds. Check the tightness of the connections before installing heat insulation or filling the system with water.
If flanges are used, provide enough clearance for the frost protection sensor drawer or the droplet separator drawer.
The flanges should be offset.
Supplying the coils
Warning: water + glycol = risk of burns and toxic if ingested
Refer to your dimensional drawing for the diameters of the connections and their positions.
Check the connections for leaks after 24 hours.