EN -
27
AQUACIAT
POWER
Name
Status
Default
Unit
Displayed text*
Description
m_dltp_a
no/yes
no
-
Low Delta Press Cir A
Low delta pressure, circuit A
m_dltp_b
no/yes
no
-
Low Delta Press Cir B
Low delta pressure, circuit B
m_night
no/yes
no
-
Night Low Noise Active
Night low noise active
m_hsm
no/yes
no
-
System Manager Active
System Manager active
m_slave
no/yes
no
-
Master Slave Active
Master/slave mode active
m_autoch
no/yes
no
-
Auto Changeover Active
Automatic changeover active
m_defr_a
no/yes
no
-
Defrost Active Circuit A
Defrost mode active, circuit A (heat pumps)
m_defr_b
no/yes
no
-
Defrost Active Circuit B
Defrost mode active, circuit B (heat pumps)
m_boiler
no/yes
no
-
Boiler Active
Boiler active
m_ehs
no/yes
no
-
Electric Heater Active
Electric heater active
m_ewtlck
no/yes
no
-
Heating Low EWT Lockout
Heating low EWT lockout
m_ice
no/yes
no
-
Ice Mode In Effect
Ice mode active
m_fastRe
no/yes
no
-
Fast Capacity Recovery
Fast capacity recovery mode (currently not available)
* Depends on the selected language (French by default).
DC Free Cooling Status Menu – DCFC_STA
Name
Status
Default
Unit
Displayed text*
Description
oat
-
-
°C / °F
OAT Free Cooling
Dry Cooler Free Cooling: OAT
lwt
-
-
°C / °F
FC Leaving Water Temp Dry Cooler Free Cooling: Leaving water temperature
wloop
-
-
°C / °F
FC Water Loop Temp
Dry Cooler Free Cooling: Water loop temperature
m_dcfc
no/yes
no
-
Free Cooling Mode Active Dry Cooler Free Cooling mode active
dcfc_cap
0 to 100
0
%
FC Capacity
Dry Cooler Free Cooling capacity
f_stage
0 to 20
0
-
Fix Speed Fans Stage
Dry Cooler Free Cooling: Fan stage (fixed speed fans)
vf_speed
0 to 100
0
%
Varifan Speed
Dry Cooler Free Cooling: Fan speed (variable speed)
pid_out
0 to 100
-
%
PID Output
Status of PID output
FC_HOUR
0 to 999999
-
hour
DCFC Operating Hours
Dry Cooler Free Cooling: Operating hours
FC_FAN1S
0 to 999999
-
-
DCFC Fan Stage 1 Start DCFC / Fan stage 1: Number of starts
FC_FAN1H
0 to 999999
-
hour
DCFC Fan Stage 1 Hours DCFC / Fan stage 1: Operating hours
FC_FAN2S
0 to 999999
-
-
DCFC Fan Stage 2 Start DCFC / Fan stage 2: Number of starts
FC_FAN2H
0 to 999999
-
hour
DCFC Fan Stage 2 Hours DCFC / Fan stage 2: Operating hours
FC_FAN3S
0 to 999999
-
-
DCFC Fan Stage 3 Start DCFC / Fan stage 3: Number of starts
FC_FAN3H
0 to 999999
-
hour
DCFC Fan Stage 3 Hours DCFC / Fan stage 3: Operating hours
FC_FAN4S
0 to 999999
-
-
DCFC Fan Stage 4 Start DCFC / Fan stage 4: Number of starts
FC_FAN4H
0 to 999999
-
hour
DCFC Fan Stage 4 Hours DCFC / Fan stage 4: Operating hours
FC_FAN5S
0 to 999999
-
-
DCFC Fan Stage 5 Start DCFC / Fan stage 5: Number of starts
FC_FAN5H
0 to 999999
-
hour
DCFC Fan Stage 5 Hours DCFC / Fan stage 5: Operating hours
FC_FAN6S
0 to 999999
-
-
DCFC Fan Stage 6 Start DCFC / Fan stage 6: Number of starts
FC_FAN6H
0 to 999999
-
hour
DCFC Fan Stage 6 Hours DCFC / Fan stage 6: Operating hours
FC_FAN7S
0 to 999999
-
DCFC Fan Stage 7 Start DCFC / Fan stage 7: Number of starts
FC_FAN7H
0 to 999999
hour
DCFC Fan Stage 7 Hours DCFC / Fan stage 7: Operating hours
FC_VFANS
0 to 999999
-
DCFC Variable Fan Start DCFC / Variable speed fan: Number of starts
FC_VFANH
0 to 999999
hour
DCFC Variable Fan Hours DCFC / Variable speed fan: Operating hours
* Depends on the selected language (French by default).
Msc Status Menu – MSC_STAT
Name
Status
Default
Unit
Displayed text*
Description
m_ecopmp
no/yes
no
-
Eco Pump Mode Active
Eco pump mode status: When this mode is active, the pump is stopped
periodically when the unit is in Standby
* Depends on the selected language (French by default).
7 - CONNECT TOUCH CONTROL: MENU STRUCTURE
Modes Menu – MODES
(continued)