ECG-UG-16-006
REVISION
DATE
PAGE
AquaCIAT LD/ILD
Modbus
Rev A
1/13/17
9 OF 20
Company private. Do not distribute outside of CIAT Corporation
Table
Item
Description
Media
Type
Address
(hex)
Format
(000C)h (32-bit)
PROTOCOL
CTRL_PNT
Control Point
HR
14
(000E)h
IEEE Float
(32-bit)
HCCONFIG
cr_sel
Cooling Reset Select
HR
18
(0012)h
Signed Integer
(32-bit)
HCCONFIG
hr_sel
Heating Reset Select
HR
20
(0014)h
Signed Integer
(32-bit)
RESETCFG
oatcr_no
OAT No Reset Value
HR
22
(0016)h
IEEE Float
(32-bit)
RESETCFG
oatcr_fu
OAT Full Reset Value
HR
24
(0018)h
IEEE Float
(32-bit)
RESETCFG
dt_cr_no
Delta T No Reset Value
HR
26
(001A)h
IEEE Float
(32-bit)
RESETCFG
dt_cr_fu
Delta T Full Reset Value
HR
28
(001C)h
IEEE Float
(32-bit)
RESETCFG
cr_deg
Cooling Reset Deg. Value
HR
30
(001E)h
IEEE Float
(32-bit)
RESETCFG
oathr_no
OAT No Reset Value
HR
32
(0020)h
IEEE Float
(32-bit)
RESETCFG
oathr_fu
OAT Full Reset Value
HR
34
(0022)h
IEEE Float
(32-bit)
RESETCFG
dt_hr_no
Delta T No Reset Value
HR
36
(0024)h
IEEE Float
(32-bit)
RESETCFG
dt_hr_fu
Delta T Full Reset Value
HR
38
(0026)h
IEEE Float
(32-bit)
RESETCFG
hr_deg
Heating Reset Deg. Value
HR
40
(0028)h
IEEE Float
(32-bit)
CP_UNABL
un_cp_a1
Compressor A1 Disable
HR
60
(003C)h
Signed Integer
(32-bit)
CP_UNABL
un_cp_a2
Compressor A2 Disable
HR
62
(003E)h
Signed Integer
(32-bit)
CP_UNABL
un_cp_a3
Compressor A3 Disable
HR
64
(0040)h
Signed Integer
(32-bit)
CP_UNABL
un_cp_b1
Compressor B1 Disable
HR
68
(0044)h
Signed Integer
(32-bit)
CP_UNABL
un_cp_b2
Compressor B2 Disable
HR
70
(0046)h
Signed Integer
(32-bit)
SETPOINT
csp1
Cooling Setpoint 1
HR
76
(004C)h
IEEE Float
(32-bit)
SETPOINT
csp2
Cooling Setpoint 2
HR
78
(004E)h
IEEE Float
(32-bit)
SETPOINT
hsp1
Heating Setpoint 1
HR
80
(0050)h
IEEE Float
(32-bit)
SETPOINT
hsp2
Heating Setpoint 2
HR
82
(0052)h
IEEE Float
(32-bit)
SETPOINT
ramp_sp
Ramp Loading
HR
84
(0054)h
IEEE Float
(32-bit)
SETPOINT
cauto_sp
Cool Changeover Setpt
HR
86
(0056)h
IEEE Float
(32-bit)
SETPOINT
hauto_sp
Heat Changeover Setpt
HR
88
(0058)h
IEEE Float
(32-bit)