ECG-UG-16-006
REVISION
DATE
PAGE
AquaCIAT LD/ILD
Modbus
Rev A
1/13/17
10 OF 20
Company private. Do not distribute outside of CIAT Corporation
Table
Item
Description
Media
Type
Address
(hex)
Format
SETPOINT
lim_sp1
Switch Limit Setpoint 1
HR
90
(005A)h
Signed Integer
(32-bit)
SETPOINT
lim_sp2
Switch Limit Setpoint 2
HR
92
(005C)h
Signed Integer
(32-bit)
SETPOINT
lim_sp3
Switch Limit Setpoint 3
HR
94
(005E)h
Signed Integer
(32-bit)
SETPOINT
min_sct
Desuperheater Min Sct
HR
96
(0060)h
IEEE Float
(32-bit)
MODBUSRS metric
Metric Unit
HR
106
(006A)h
Signed Integer
(32-bit)
MODBUSRS swap_b
Swap Bytes
HR
108
(006C)h
Signed Integer
(32-bit)
MODBUSRS real_typ
Real type management
HR
110
(006E)h
Signed Integer
(32-bit)
MODBUSIP
metric
Metric Unit
HR
112
(0070)h
Signed Integer
(32-bit)
MODBUSIP
swap_b
Swap Bytes
HR
114
(0072)h
Signed Integer
(32-bit)
MODBUSIP
real_typ
Real type management
HR
116
(0074)h
Signed Integer
(32-bit)
GENUNIT
SP_OCC
Setpoint Occupied?
IR
0
(0000)h
Signed Integer
(32-bit)
GENUNIT
CHIL_S_S
Net.: Cmd Start/Stop
IR
2
(0002)h
Signed Integer
(32-bit)
GENUNIT
CHIL_OCC
Net.: Cmd Occupied
IR
4
(0004)h
Signed Integer
(32-bit)
GENUNIT
EMSTOP
Emergency Stop
IR
6
(0006)h
Signed Integer
(32-bit)
GENUNIT
CTRL_TYP
Local=0 Net.=1 Remote=2
IR
8
(0008)h
Signed Integer
(32-bit)
GENUNIT
STATUS
Running Status
IR
10
(000A)h
Signed Integer
(32-bit)
GENUNIT
min_left
Minutes Left for Start
IR
12
(000C)h
IEEE Float
(32-bit)
GENUNIT
HEATCOOL
Heat/Cool status
IR
14
(000E)h
Signed Integer
(32-bit)
GENUNIT
SP_SEL
Setpoint Select
IR
16
(0010)h
Signed Integer
(32-bit)
GENUNIT
CAP_T
Percent Total Capacity
IR
18
(0012)h
Signed Integer
(32-bit)
GENUNIT
CAPA_T
Circuit A Total Capacity
IR
20
(0014)h
Signed Integer
(32-bit)
GENUNIT
CAPB_T
Circuit B Total Capacity
IR
22
(0016)h
Signed Integer
(32-bit)
GENUNIT
DEM_LIM
Active Demand Limit Val
IR
24
(0018)h
Signed Integer
(32-bit)
GENUNIT
SP
Current Setpoint
IR
26
(001A)h
IEEE Float
(32-bit)
GENUNIT
CTRL_PNT
Control Point
IR
28
(001C)h
IEEE Float
(32-bit)
GENUNIT
ALM
Alarm State
IR
30 Signed Integer