5 - ELECTRICAL DATA
AQUACIAT CALEO™ TD
80
100
120
150
200
300
Power circuit
Nominal power supply
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit supply
24 V, via internal transformer
Maximum start-up current (Un)
(1)
Standard unit
A
102
130
172
203
158
243
Unit with electronic starter option
A
54
69
92
103
97
144
Unit power factor at maximum capacity
(2)
0,82
0,83
0,87
0,87
0,83
0,87
Maximum unit power input
(2)
kW
12
16
21
25
32
48
Nominal unit current draw
(3)
A
16
20
25
30
42
57
Maximum unit current draw (Un)
(4)
A
21
27
35
41
56
79
Maximum unit current draw (Un-10%)
(5)
A
22
29
38
45
60
86
(1) Maximum instantaneous start-up current (maximum operating current of the comp fan c locked rotor current of the compressor).
(2) Power input, compressor and fan, at the unit operating limits (saturated suction temperature 10°C, saturated condensing temperature 65°C) and nominal voltage
of 400V (data given on the unit nameplate).
(3) Standardised Eurovent conditions: evaporator entering/leaving water temperature 40°C/45°C, outside air temperature db/wb = 7°C/6°C.
(4) Maximum unit operating current at maximum unit power input and 400V (values given on the unit nameplate).
(5) Maximum unit operating current at maximum unit power input and 360V.
5.1 - Compressor usage and electrical data for standard units
Compressor
I Nom
I Max
I Max
LRA
(1)
LRA
(2)
Cosine
080
100
120
150
200
300
(Un)
(Un-10%)
A
A
phi max.
ZH24KVE
13,6
18,3
20,3
99
51
0,85
1
-
-
-
-
-
ZH33KVE
17,3
24,2
26,9
127
66
0,85
-
1
-
-
2
-
ZH40KVE
20,4
30,0
33,2
167
87
0,89
-
-
1
-
-
-
ZH48KVE
24,9
36,0
40,0
198
97
0,89
-
-
-
1
-
2
Legend
I Nom
Nominal current draw at Eurovent conditions (see definition of conditions under nominal unit current draw), A
I Max
Maximum operating current at 360 V, A
(1)
Locked rotor current at nominal voltage, A
(2)
Locked rotor current at nominal voltage, electronic starter
5.2 - Short-circuit stability current (TN system
(1)
) - standard unit (with main disconnect
without fuse)
TD
080
100
120
150
200
300
Value without upstream protection
Short-term current at 1s (Icw)
kA rms
0,6
0,6
1,26
1,26
1,26
2
Admissible peak current (Ipk)
kA pk
4,5
4,5
6
6
6
10
Maximum value with upstream protection by circuit breaker
Conditional short-circuit current (Icc)
kA rms
7
7
7,7
7,7
6,1
10
Circuit breaker - Compact range
40
40
50
63
80
100
Reference number
(2)
5SY6340-7 5SY6340-7 5SY4350-7 5SY4363-8 5SP4380-7 5SP4391-7
Value with upstream protection (fuses)
Conditional short-circuit current Icc - kA rms
kA rms
50
50
50
50
14,5
22
Fuse (gL/gG)
40
40
63
63
80
125
(1) Earthing system type
(2) If another current limitation protection system is used, its time-current and thermal constraints (l²t) trip characteristics must be at least equivalent to those of the
recommended
circuit
breaker.
The short circuit stability current values above are suitable with TN system.
EN-17 AQUACIAT
CALÉO™
TD