dIXEL

 

Installing and Operating Instructions 

1592027320

 

 

1592027320 XW20LS RTC GB r1.0 10.07.2008.doc 

XW20LS 

2/5 

3.

 

Use “

UP

” or “

DOWN

” to change its value. 

4.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.6

 

THE HIDDEN MENU 

The hidden menu Includes all the parameters of the instrument. 

6.6.1  HOW TO ENTER THE HIDDEN MENU 

1.

 

Enter the Programming mode by pressing the 

Set

 + 

n

 keys for 3s (the “

°C” or “°F”

 LED starts 

blinking). 

2.

 

Released the keys, then push again the Set+

n

 keys for more than 7s. The Pr2 label will be 

displayed immediately followed from the HY parameter.  

NOW YOU ARE IN THE HIDDEN MENU.

 

3.

 

Select the required parameter. 

4.

 

Press the “

SET

” key to display its value 

5.

 

Use 

or 

n

 to change its value. 

6.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + 

or wait 15s without pressing a key. 

NOTE1: 

if none parameter is present in Pr1, after 3s the “noP” message is displayed. Keep the keys 

pushed till the Pr2 message is displayed.  

NOTE2

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.6.2  HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE 
FIRST LEVEL AND VICEVERSA. 

Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” 
(user level) by pressing 

“SET + 

n

.  

In HIDDEN MENU when a parameter is present in First Level the decimal point is on. 

6.7

 

HOW TO LOCK THE KEYBOARD 

1. 

 

Keep pressed for more than 3 s the 

UP

 +  

DOWN

 keys. 

2. 

 

The “POF” message will be displayed and the keyboard will be locked. At this point it will be 
possible only to see the set point or the MAX o Min temperature stored 

3. 

 

If a key is pressed more than 3s the “POF” message will be displayed. 

6.8

 

TO UNLOCK THE KEYBOARD 

Keep pressed together for more than 3s the 

and 

n

 keys, till the 

“Pon” 

message will be 

displayed. 

6.9

 

THE CONTINUOUS CYCLE 

When defrost is not in progress, it can be activated by holding the “

o

” key pressed for about 3 

seconds. The compressor operates to maintain the “

ccS

” set point for the time set through the “

CCt

” 

parameter. The cycle can be terminated before the end of the set time using the same activation key 

o

” for 3 seconds. 

6.10

 

THE ON/OFF FUNCTION 

 

 

With “

onF = oFF

”, pushing the 

ON/OFF

 key, the instrument is switched off. The 

“OFF” 

message is displayed. In this configuration, the regulation is disabled.  
To switch the instrument on, push again the ON/OFF key. 

 

WARNING: Loads connected to the normally closed contacts of the relays are always 

supplied and under voltage, even if the instrument is in stand by mode.  

7.

 

PARAMETERS 

rtc  Real time clock menu (only for controller with RTC): 

to set the time and date and defrost 

start time. 

REGULATION 
Hy Differential

: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. Compressor Cut IN 

is Set Point + differential (Hy). Compressor Cut OUT is when the temperature reaches the set 
point. 

LS  Minimum set point:

 (- 50°C÷SET/-58°F÷SET): Sets the minimum value for the set point. 

US Maximum set point: 

(SET÷110°C/ SET÷230°F). Set the maximum value for set point. 

Ot  Thermostat probe calibration

: (-12.0÷12.0°C; -120÷120°F) allows to adjust possible offset of 

the thermostat probe. 

P2P  Evaporator probe presence: n

= not present:  

y=

 present: 

OE Evaporator probe calibration:

 (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of 

the evaporator probe. 

P3P Third probe presence (P3): n

= not present:, the terminals operate as digital input.; 

y=

 

present:, the terminals operate as third probe. 

O3 Third probe calibration  (P3):

 (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of 

the third probe. 

OdS Outputs activation delay at start up:

 (0÷255min) This function is enabled at the initial start up 

of the instrument and inhibits any output activation for the period of time set in the parameter.  

AC  Anti-short cycle delay

: (0÷50 min) minimum interval between the compressor stop and the 

following restart. 

rtr  Percentage of the second and first probe for regulation (0÷100; 100 = P1, 0 = P2 ): 

it 

allows to set the regulation according to the percentage of the first and second probe, as for the 
following formula (rtr(P1-P2)/100 + P2). 

CCt Compressor ON time during continuous  cycle: 

(0.0÷24.0h; res. 10min) Allows to set the 

length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be 
used, for instance, when the room is filled with new products. 

CCS Set point for continuous cycle: 

(-50÷150°C) it sets the set point used during the continuous 

cycle. 

COn Compressor ON time with faulty probe: 

(0÷255 min) time during which the compressor is 

active in case of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: 

(0÷255 min) time during which the compressor is 

OFF in case of faulty thermostat probe. With COF=0 compressor is always active. 

CH  Type of action: 

CL = cooling; Ht = heating.

 

DISPLAY 

CF Temperature measurement unit: 

 

°C=

Celsius; 

°F

=Fahrenheit. WARNING: When the 

measurement unit is changed the SET point and the values  of the parameters Hy, LS, US, Ot, 
ALU and ALL have to be checked and modified if necessary). 

rES  Resolution (for °C)

: (in = 1°C; dE = 0.1 °C) allows decimal point display. 

Lod Instrument display

: (P1; P2, P3, P4,  SET, dtr): it selects which probe is displayed by the 

instrument: 

P1

 = Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = Third probe(only for model 

with this option enabled); 

P4

 = NOT SET IT,

 SET

 = set point;  

dtr

 = percentage of visualization. 

rEd  X- REP display (

optional

)

: (P1; P2, P3, P4,  SET, dtr): it selects which probe is displayed by 

X- REP: 

P1

 = Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = Third probe(only for model with 

this option enabled); 

P4

 = NOT SET IT,

 SET

 = set point;  

dtr

 = percentage of visualization. 

dLy Display delay: 

(0 ÷20.0m; resul. 10s) when the temperature increases, the display is updated 

of 1 °C/1°F after this time. 

dtr  Percentage of the second and first probe for visualization when Lod = dtr (0÷100; 100 = 

P1, 0 = P2 ): if Lod = dtr 

it allows to set the visualization according to the percentage of the 

first and second probe, as for the following formula (dtr(P1-P2)/100 + P2). 

DEFROST 
EdF  Defrost mode (only for controller with RTC):

  

rtc 

Real Time Clock mode

. Defrost time 

follows 

Ld1÷Ld6

 parameters on workdays and 

Sd1÷Sd6

 on holidays. 

 in

 = 

interval mode

. The defrost starts when the time “

Idf

” is expired. 

dFP Probe selection for defrost termination: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

evaporator probe; 

P3

 =configurable probe; 

P4

 = NOT SET IT. 

dtE  Defrost termination temperature

: (-50÷50 °C/ -58÷122°F) (Enabled only when EdF=Pb) sets 

the temperature measured by the evaporator probe, which causes the end of defrost. 

IdF  Interval between defrost cycles

: (0÷120h) Determines the time interval between the 

beginning of two defrost cycles. 

MdF  (Maximum) length for defrost

: (0÷255min) When 

P2P = n

, (not evaporator probe: timed 

defrost) it sets the defrost duration, when 

P2P = y

 (defrost end based on temperature) it sets 

the maximum length for defrost. 

dFd  Temperature displayed during defrost

: (

rt

 = real temperature; 

it

 = temperature at defrost 

start; 

SEt

 = set point; 

dEF

 = “dEF” label) 

dAd MAX display delay after defrost

: (0÷255min). Sets the maximum time between the end of 

defrost and the restarting of the real room temperature display. 

ALARMS 
ALP  Probe selection for alarm

nP

 = no probe, the temperature alarms are disabled; 

P1 = 

Probe 1 

(Thermostat probe); 

P2 = 

Probe 2 (evaporator probe); 

P3 = 

Probe 3 (display probe); 

P4 = 

NOT 

SET IT. 

ALC  Temperature alarms configuration:

 (Ab; rE) 

 

Ab

= absolute temperature: alarm temperature is given by the ALL or ALU values.  

rE

 = 

temperature alarms are referred to the set point. Temperature alarm is enabled when the 
temperature exceeds the “SET+ALU” or “SET-ALL” values. 

ALU  MAXIMUM temperature alarm

: (SET÷110°C; SET÷230°F) when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

ALL Minimum temperature alarm

: (-50.0 ÷ SET °C; -58÷230°F when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

AFH Differential for temperature alarm recovery: 

(0,1÷25,5°C; 1÷45°F) Intervention differential 

for recovery of temperature alarm. 

ALd  Temperature alarm delay

: (0÷255 min) time interval between the detection of an alarm 

condition and alarm signalling. 

dAo Exclusion of temperature alarm at start-up

: (from 0.0 min to 23.5h) time interval between the 

detection of the temperature alarm condition after instrument power on and alarm signalling. 

CONDENSER TEMPERATURE ALARM 
AP2  Probe selection for temperature alarm of condenser: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

evaporator probe; 

P3

 =configurable probe; 

P4

 = NOT SET IT. 

AL2 Low temperature alarm of condenser

:

 

(-55÷150°C) when this temperature is reached the 

LA2 alarm is signalled, possibly after the Ad2 delay. 

Au2 High temperature alarm of condenser

:

 

(-55÷150°C) when this temperature is reached the 

HA2 alarm is signalled, possibly after the Ad2 delay. 

AH2 Differential for temperature condenser alarm recovery

:

 

(0,1÷25,5°C; 1÷45°F) 

Ad2 Condenser temperature alarm delay

: (0÷255 min) time interval between the detection of the 

condenser alarm condition and alarm signalling. 

dA2 Condenser temperature alarm exclusion at start up

: (from 0.0 min to 23.5h, res. 10min) 

bLL  Compressor off with low temperature alarm of condenser

:

 n = no: 

compressor keeps on 

working

; Y = yes, 

compressor is switched off till the alarm is present, in any case regulation 

restarts after AC time at minimum.

 

AC2 Compressor off with high temperature alarm of condenser

:

 n = no: 

compressor keeps on 

working

; Y = yes, 

compressor is switched off till the alarm is present, in any case regulation 

restarts after AC time at minimum.

 

DIGITAL INPUT 
i1P  Digital input polarity: oP: 

the digital input is activated by opening the contact; 

CL: 

the digital 

input is activated by closing the contact.

 

i1F Digital input configuration: EAL

= external alarm: “EA” message is displayed; 

bAL

= serious 

alarm “CA” message is displayed. 

PAL

= pressure switch alarm, “CA” message is displayed; 

dor

= door switch function; 

dEF

= activation of a defrost cycle; 

AUS

=not enabled; 

Htr

= kind of 

action inversion (cooling – heating); 

FAn

=

 not set it; ES

=

 

Energy saving; 

HdF 

=

 

Holiday 

defrost (enable only with RTC); 

onF = 

to switch the controller off. 

did 

(0

÷

255 min) 

with

 

i1F= EAL or i1F = bAL digital input alarm delay (1-3):

 delay between the 

detection of the external alarm condition and its signalling. 

with

 

i1F= dor: door open signalling delay 

with i1F= PAL: time for pressure switch function: 

time interval to calculate the number of 

the pressure switch activation. 

nPS Pressure switch number:

 (0 

÷

15) Number of activation of the pressure switch, during the “

did

” 

interval, before signalling the alarm event (i1F= PAL).  

If the nPS activation in the did time is reached, switch off and on the instrument to 

restart normal regulation. 

odc  Compressor status when open door:

  

no,

 

Fan

 = normal; 

CPr, F_C

 = Compressor OFF.  

rrd  Outputs restart after doA alarm: no= 

outputs not affected by the doA alarm;  

yES = 

outputs 

restart with the doA alarm. 

HES Temperature increase during the Energy Saving cycle: 

(-30,0°C

÷

30,0°C) it sets the increasing value of the set point during the Energy Saving cycle.  

TO SET CURRENT TIME AND WEEKLY HOLIDAYS (ONLY FOR MODELS WITH RTC) 
Hur Current 

hour 

(0 ÷ 23 h) 

Min Current 

minute

 (0 ÷ 59min) 

Содержание 6040 Series

Страница 1: ...Refrigerated Pastry Showcase 6040 SERIES Maintenance And Use Manual CIAMspa 06081 Petrignano d Assisi PG Italy tel 075 80161 Fax 075 8016215 http www ciamgroup it e mail info ciamgroup it...

Страница 2: ...or refrigerators freezers and ice machines 1 4 RESPONSIBILITY Ciam declines any responsibility relevant to damages on persons animals and or products in case of No respect of in force norms Installati...

Страница 3: ...ong stock have not to be ascribed to the manufacturer 3 4 DISPLAY CABINET POSITION The refrigerated display cabinet needs particular environmental conditions in order to offer the right performance so...

Страница 4: ...et in order to make easy any type of check and maintenance operations When the condensing units are external will be necessary a frame holder that has to be fixed in a proper way and eventually added...

Страница 5: ...a wet cloth weekly Additional defrost Under particular conditions of temperature and humidity the frost that normally forms on the evaporator and fans might increase in volume so leading to a faulty f...

Страница 6: ...G ELEMENT SUCTION AIR GLASS HEATING ELEMENT OUTLET AIR HEATING ELEMENT REAR GLASS HEATING ELEMENT INTERNAL GLASS HEATING ELEMENT FRONT GLASS UPPER FRAME HEATING ELEMENT FRONT GLASS LATERAL LOWER FRAME...

Страница 7: ......

Страница 8: ......

Страница 9: ...s length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 3 CONTROL OF EVAPORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C_n fans will switch ON...

Страница 10: ...THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA Each parameter present in the HIDDEN MENU can be removed or put into THE FIRST LEVEL user level by pressing SET n In HIDDEN MENU when a parameter is p...

Страница 11: ...ture alarm delay 0 255 min time interval between the detection of an alarm condition and alarm signalling dAO Exclusion of temperature alarm at start up from 0 0 min to 23 5h time interval between the...

Страница 12: ...TORING SYSTEMS The TTL serial line available through the HOT KEY connector allows by means of the external TTL RS485 converter XJ485 CX to connect the instrument to a monitoring system ModBUS RTU comp...

Страница 13: ...ous cycle duration 0 0 24 0h 0 0 Pr2 CCS Set point for continuous cycle 55 0 150 0 C 67 302 F 5 Pr2 COn Compressor ON time with faulty probe 0 255 min 15 Pr2 COF Compressor OFF time with faulty probe...

Страница 14: ...50 min nu 13 0 rtc Sd3 3rd holiday defrost start 0 23h 50 min nu 21 0 rtc Sd4 4th holiday defrost start 0 23h 50 min nu 0 0 rtc Sd5 5th holiday defrost start 0 23h 50 min nu 0 0 rtc Sd6 6th holiday de...

Страница 15: ...standard way for controller without RTC with EdF rtc the defrost is made in real time depending on the hours set in the parameters Ld1 Ld6 on workdays and in Sd1 Sd6 in holidays Other parameters are u...

Страница 16: ...visualization rEd X REP display optional P1 P2 P3 P4 SET dtr it selects which probe is displayed by X REP P1 Thermostat probe P2 Evaporator probe P3 Third probe only for model with this option enabled...

Страница 17: ...will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired 8 6 INVERSION OF THE KIND OF ACTION HEATING COOLING i1F Htr This function all...

Страница 18: ...XW20LS DIRECT CONNECTIONS OF LOAD Supply 120Vac or 24Vac connect to terminals 5 6 The X REP output is optional 17 DEFAULT SETTING VALUES Label Name Range C F Level Set Set point LS US 3 0 rtc Real tim...

Страница 19: ...start 0 23h 50 min nu 0 0 rtc Sd6 6th holiday defrost start 0 23h 50 min nu 0 0 rtc Adr Serial address 1 247 1 Pr2 PbC Kind of probe Ptc ntc ntc Pr2 onF on off key enabling nu oFF ES oFF Pr2 dP1 Room...

Отзывы: