background image

 

MetCam Technical Manual

 

Document P/N A1604870010 

 

 

4

Use 

 

4.1

Installation Prerequisites 

A correct installation is crucial for MetCam's effectiveness. Note the following important guidelines: 

 

MetCam has a field of view (FOV) of 68 degrees Horizontal and 23 degrees Vertical 

 

MetCam should be mounted at an elevated position looking downwards towards the monitored area. The minimal 
recommended angle is 15 degrees below the horizontal. 

 

The optimal distance to the monitored area is 20-30 meters. The permissible operating range is 10-50 meters. 

 

MetCam FOV should be free of objects which are at a distance of less than 5 meters from it. 

 

MetCam should be mounted to a stable structure free of excessive vibration. Good choices would be a steel 
bulkhead, brick wall, concrete post or a rigid steel structure. Avoid flimsy metal structures that may flex, or 
wooden structures that may warp.  

 

If MetCam is installed at a location where it is exposed to direct rain/snow fall or sunlight, use of the optional 
sun/rain shield is required. 

 

Select the installation location such that the line-of-sight from it, to the monitored area, is free from obstacles. 
Since Methane has buoyancy, it is recommended to also have a free line-of-sight to the area above the monitored 
area. 

 

Avoid locations where high levels of contaminants will 

persistently be blown onto the unit’s optics. Potential 

sources of heavy contamination include generator/turbine exhausts, flarestacks, drilling equipment, process 
vents/chimneys etc. If sources of heavy contamination cannot be avoided, consider providing good access for 
more routine cleaning 

 

Locations where there is a significant likelihood of equipment, personnel or moving objects accidentally knocking 
MetCam out of alignment should be avoided. If such locations cannot be avoided, measures including improved 
mechanical protection and warning notices should be considered 

 

MetCam is to be connected to a 24 VDC power source. The details of this source are described in 

Section 

‎4.1.1 

 

 

To benefit from its imaging capabilities, MetCam should be connected, via a LAN cable equivalent to CAT5E (or 
higher), or via a Wi-Fi connection, to an ONVIF client. 

 

MetCam can be connected with 4-20 mA to the control unit. 

 

Maximal CAT5E cable length is 100 meters. 

4.1.1 

Electrical Installation Prerequisites 

MetCam complies with the EMC requirements. In order to maintain compliance with these standards it is essential that 
the electrical installation of MetCam is engineered correctly. 

To fully comply with EMC directive and protect against radio frequency interference (RFI) or electromagnetic interference 
(EMI), the cable to MetCam must be shielded and MetCam must be grounded. The shield should be grounded at the 
MetCam end. All cables to MetCam must be well shielded to comply with EMC requirements.  

Electrical installation standards vary for different countries, companies and applications and it is the responsibility of the 
installation design authority to determine the applicable standards and ensure compliance with them. When designing 
electrical installations for MetCam it is recommend that the installation design authority considers that any earthing regime 
employed must avoid earth loops. 

MetCam must be either connected to a SELV/PELV system, or directly connected to an apparatus compliant with IEC 
60950 series, IEC 610101-1, or equivalent 24 V power supply.  
MetCam includes an earthing point, on the bottom side of the enclosure. 

Содержание MetCam A160100 0 Series

Страница 1: ...MetCam Technical Manual Document P N A1604870010 1 MetCam Models A160100xxx0 Instructions for Use Manual Rev B Feb 2020...

Страница 2: ...Type Marking 6 4 Use 7 4 1 Installation Prerequisites 7 4 1 1 Electrical Installation Prerequisites 7 4 2 Installation 8 4 2 1 Handling 8 4 2 2 Installing the Tilt Mount 9 4 2 3 Connecting MetCam to t...

Страница 3: ...ocument P N A1604870010 3 5 Troubleshooting 14 6 Maintenance 14 6 1 Optical Cleaning Instructions 14 6 2 Exterior Cleaning Instructions 14 6 3 Periodic Procedures 15 7 Disposal 15 8 Technical Data 15...

Страница 4: ...ational rules and regulations associated with this product Only trained and competent personnel who are familiar with local codes and practice are permitted to inspect repair and service the product a...

Страница 5: ...d The threaded back plate shall be tightened all the way to the stopping shoulder and secured against self loosening by tightening the set screw using hex 0 050 Lens guards must always be applied and...

Страница 6: ...as a supplementary detection device for total risk reduction The limitations of this technology must be assessed with respect to their ability or inability to determine the concentration of gas There...

Страница 7: ...here is a significant likelihood of equipment personnel or moving objects accidentally knocking MetCam out of alignment should be avoided If such locations cannot be avoided measures including improve...

Страница 8: ...and wire MetCam see Section 4 3 1 MetCam power up see Section 4 4 4 2 1 Handling Warranty void if opening MetCam enclosure other than the back cover used for accessing the electrical connections to th...

Страница 9: ...mount is not symmetrical make sure to install it in the correct orientation Note that the tilt mount does not include a pan degree of freedom so it is important to align it to the monitored area when...

Страница 10: ...eld optional item should be mounted after connecting MetCam to the tilt mount It does not interfere with wiring or with aiming MetCam 4 2 5 Installing the Wi Fi Antenna MetCam can be ordered with an o...

Страница 11: ...the back of MetCam needs to be opened for accessing the terminal block and then needs to be closed properly so that the unit will retain its explosion flame proof certification The arrow in the pictur...

Страница 12: ...vailable for connecting the cable shield on the cable gland entrance collar Terminal Block Pin Assignment Pin Marking on Terminal Block Description 1 Voltage input Max 32 V 2 Voltage input 3 4 20 mA H...

Страница 13: ...cation of the Indicator LED the green arrow is pointing to it 4 5 4 20 mA Signaling and LED Status MetCam uses a stepped output and needs to be installed as a 4 wire transmitter The signaling range is...

Страница 14: ...reflector periodically The frequency of cleaning operations depends upon the local environmental conditions and specific applications It is recommended to visually inspect and clean if deemed necessa...

Страница 15: ...t be disposed of as household waste You can return this product to CI Systems free of charge For information please contact the national marketing organizations or CI Systems 8 Technical Data Mechanic...

Страница 16: ...temperature range w o wifi A1601001340 Extended temperature range wifi M25 Gland Entrance MetCam Models P N Description A1601000200 Standard temperature range w o wifi A1601000240 Standard temperature...

Отзывы: