background image

CHRONOMITE INSTANT-FLOW        

 

      

WATER HEATER 

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) 

(Before installation, compare electrical needed for the model of heater selected) 

 
TABLE 1 

 

 
 
 
 
 
 
 
Instant-Flow       

Specifications: 

 Dimensions:    

 

6¼” x 9 

5/8”

 x 2 ¾

 

 

Weight: 

  5 

lbs. 

 Materials: 

 

 

Rugged cast aluminum alloy casing, Celcon waterways, nichrome parts 

 Color:  

 

 

White (unless stainless steel housing) 

 Pipe Fittings:   

 

Female 

¼” 

NPT standard pipe thread 

 Pressure Requirements: 

25 PSI Minimum, 150 PSI Maximum (300 PSI tested) No pressure relief valve needed 
unless required by local codes. 

 Maximum Operating Temp: 

140°F 

 Flow Switch Activation: 

.4 GPM   

 Flow Switch De-Activation: 

.35 GPM 

 Listings:   

 

 

UL, HUD, IAPMO  

 
 

 
 
 
 
 
 
 
 
 

THE MANUFACTURER OF THIS WATER HEATER WILL NOT BE LIABLE FOR ANY DAMAGES 
DUE TO THE FAILURE TO FOLLOW THESE INSTALLATION AND OPERATION INSTRUCTIONS. 

 
CAUTION:  

BEFORE BEGINNING THE INSTALLATION: 

 

A) 

Turn off the circuit breaker to avoid dangerous electrical shocks. 

B) 

Turn off the water supply.

 

 

1.  Remove electrical access cover. Attach conduit to the conduit access hole. Then feed wires. Do not attach wiring.  
2.  Mount unit horizontally against the wall so the silver label reads correctly (See Fig. 1). Mount with four screws 

through the flanges located on each corner using molly anchors or fasteners.                                             

CAUTION: Heating elements may burn out if unit is not mounted horizontally

3.  Connect plumbing. Use 

¼” 

tapered national pipe thread at cold water inlet and hot water outlet (See Fig. 1). Use 

compression fittings supplied for ease of installation.  Do not apply heat to these fittings.  

4.  Run water through the unit to expel all air bubbles. Check for leaks at all fitting joints. 
5.  Connect wiring. Attach ground wire to center terminal and hot wires to outer terminals (See Fig. 3) 
6.  Replace electrical access cover. Turn on the circuit breaker. The unit is now ready for use. 
7.  Local plumbing and electrical codes must be followed in the installation of this water heater and it’s accessories. 
8.  Failure to comply with code requirements voids the warranty. 
9.  Failure to install faucet flow control as shown on Fig. 2 will cause unsatisfactory operation of the heater. 

 

Model No. 

Wattage 

Voltage 

Breaker  

Size 

SR-15L 1800 110/120 15A 
SR-15L 4150  277  15A 
SR-20L 2400 110/120 20A 
SR-20L 4160  208  20A 
SR-20L 4800 220/240 20A 
SR-20L 5540  277  20A 
SR-30L 3600 110/120 30A 