3
ELECTRIC SHOCK HAZARD. Any installation involv-
ing electric heaters must be performed by a quali-
fied person and must be effectively grounded in
accordance with the National Electrical Code to
eliminate shock hazard.
Note:
All wiring should be done in accordance with local codes
and the National Electrical Code by a qualified person.
1.
Electrical wiring enters heater case through 7/8” opening in end of
heater.
2.
Grounding conductor, with green insulation, should be secured to
grounding screw located on case.
OPERATION
HAZARD OF FIRE OR DISCOLORATION OF TEM-
PERATURE SENSITIVE FABRICS. Keep combustible
materials and such fabrics at least 4” away from
front of cover or above cover.
FIRE HAZARD. This heater is not intended for use in
hazardous atmospheres where flammable vapors,
gases, liquids or other combustible atmospheres are
present as defined in the National Electrical Code.
Failure to comply can result in explosion or fire.
ELECTRIC SHOCK HAZARD. Disconnect all power
before attempting to service this heater.
1.
Following long periods of idleness, heater should be vacuumed
before start-up to remove accumulated combustible particles
which will incinerate causing smoking and consequent wall dis-
coloration.
2.
If heater is located in areas of heavy traffic, furnish suitable heater
guard (wall mounted pipe rail in front of case, for example) to pre-
vent damage to heater.
MAINTENANCE
WIRING
RENEWAL PARTS IDENTIFICATION
Reflector
Wall
Element
Air Space Between Wall and Heat
In
su
lating
In
su
lating
H
e
at
er
Mo
de
l
Volt
s
Watt
s
H
e
ating El
e
m
e
nt
B
us
hing
B
us
hing
Cov
er
120
1000
SE-1850 – 120V - 500W (2)
032-010978-001 (4)
032-010978-002 (4)
152-108257-001
H-1801
240
1000
SE-1850 – 240V - 500W (2)
032-010978-001 (4)
032-010978-002 (4)
152-108257-001
480
1000
SE-1850 – 240V - 500W (2)
032-010978-001 (4)
032-010978-002 (4)
152-108257-001
120
1500
SE-2475 – 120V - 750W (2)
032-010978-001 (4)
032-010978-002 (4)
152-108257-002
H-2405
240
1500
SE-2475 – 240V - 750W (2)
032-010978-001 (4)
032-010978-002 (4)
152-108257-002
480
1500
SE-2475 – 240V - 750W (2)
032-010978-001 (4)
032-010978-002 (4)
152-108257-002
120
2000
SE-2450 – 120V - 500W (4)
032-010978-001 (8)
032-010978-002 (8)
152-108257-003
H-2406
240
2000
SE-2450 – 240V - 500W (4)
032-010978-001 (8)
032-010978-002 (8)
152-108257-003
480
2000
SE-2450 – 240V - 500W (4)
032-010978-001 (8)
032-010978-002 (8)
152-108257-003
120
3000
SE-2475 – 120V - 750W (4)
032-010978-001 (8)
032-010978-002 (8)
152-108257-003
H-2407
240
3000
SE-2475 – 240V - 750W (4)
032-010978-001 (8)
032-010978-002 (8)
152-108257-003
480
3000
SE-2475 – 240V - 750W (4)
032-010978-001 (8)
032-010978-002 (8)
152-108257-003
1
3
5
4