Operating the Device
Chloride Linear Plus Series Rack-mount UPS User Instruction Manual
20
3. Connect the UPS output terminals to the load distribution.
Fig. 12: Linear Plus Parallel Diagram
Third step
1. Remove cover of the parallel port of all parallel devices for linking between the UPS
2. Use the 25 pin standard control cable (supplied with UPS) to connect from one of the parallel ports.
NOTE: Parallel UPS are connected in line, not in a circle, i.e.: 2 cables connect 3 UPS units, 1 cable
connects 2 UPS.
Fourth step
1. Close all the input breakers of all parallel UPSs.
2. Close all battery breakers on all extension battery cabinets to the “ |” position.
3. Close the mains circuit breakers to each of the UPSs.
4. The unit will initiate a self-test for approximately 15 seconds. Wait for the yellow BYPASS LED to
illuminate.
5. Press the button
on the first UPS control panel for a minimum of 1 second.
6. Repeat the UPS start-up procedure (step 5) on the second and on third UPS, if present. At this point
all the bypass indicators are extinguished. All inverter indicators illuminate indicating that all
parallel UPS inverters are running. The load is spread evenly across all the UPSs.
In addition to the “LINE” and “BYPASS” LEDs the “LOAD” LED is now illuminated. After a few
seconds the “INVERTER” LED is illuminated and the “BYPASS” LED is extinguished. The UPS is now
in ON-LINE operation. The load is spread evenly across all the UPSs.
L
L/N
S2
S1
Remove
jumper
s1s2
Mains Power
Distribution
Cb #3
Cb #2
Load
Distribution
Remove
jumper
s1s2
Remove
jumper
s1s2
S2
S1
S2
S1
Cb #1
Parallel
Connector
Parallel
Connector
P
a
ra
lle
l
c
a
b
le #1
Pa
ra
lle
l
ca
b
le #
2
Parallel
Connector
UPS #1
UPS #2
UPS #3
L
L
L/N
L/N
L
L
L
L/N
L/N
L/N
Cb
Cb
Cb
Optional
Individual Output
Circuit Breakers
Содержание LP061XHR
Страница 1: ......
Страница 3: ......
Страница 5: ......
Страница 33: ...Troubleshooting Chloride Linear Plus Series Rack mount UPS User Instruction Manual 28 ...