Installation
Chloride Linear Plus Series Rack-mount UPS User Instruction Manual
8
Installation Data
Table 3. Environment data
Ambient temperature
+32°F to +104°F (0 °C to +40 °C)
Relative humidity (w/o condensing at 20°C)
90%
Max. altitude (w/o derating)
1000 m a.s.l.
Cable inlet
bottom at the rear side
Air inlet
front
Air outlet
rear
Table 4. Electrical data Linear Plus Rack-mount 6 kVA/10 kVA
UPS-TYPE
Linear Plus
Rack-mount 6 kVA
Linear Plus
Rack-mount 10 kVA
Electrical Data
Rating
6 kVA
10 kVA
Input
Voltage
208, 220, 230, 240 VAC, 1 phase
Frequency
50/60Hz
±
5%,
automatic frequency sensing
Current @ 208 VAC
29 A
48 A
Battery
external
Type
a
External battery
packs only (1 to 5
packs)
External battery
packs only (1 to 5
packs)
Voltage/Ah
Type
240V/ 20x (12V/8 Ah)
Yuasa Rew 45-12FR
Output
Voltage
208, 220, 230, 240V
±
2%
Frequency with mains
control
see input frequency
Frequency with internal
clock
50/60Hz
±
0.5%
Nominal current at
cos
ϕ
= 0.7 and 208 V
28.8 A
48 A
General
Over voltage category
II
Protection class
IP 20
Cooling
Ventilator
a. use battery type for replacement purpose also. No other type permitted
Содержание LP061XHR