INSTRUCTIONS – INSTALLATION

 

1.

 

Mount exit enclosure to wall using (4) thru holes or optional mounting feet. (See Figure 3). 

2.

 

Remove cover screws (2) and open cover. (See Figures 1 and 2). 

3.

 

Dismount exit lens by removing lens screws (4). (See Figures 1 and 2). 

4.

 

Connect ¾” conduit supply to ¾” hub on unit. 

5.

 

Hookup AC service to the connector assembly as follows: 

 

  120 VAC OPERATION 

 

277 VAC OPERATION 

 

Black Wire 

}

- 120V Line

 

Blue Wire 

}

- 277V Line 

 

Black Wire 

Blue Wire 

 

White Wire 

- Common 

White Wire 

- Common 

 

Green Wire 

- Ground 

Green Wire 

- Ground 

      Unused primary wire must be insulated individually to prevent shorting. 

6.

 

If Fire Alarm Flasher is used: 

a.

 

Connect WHITE wire to 24VDC Positive and 24VDC Negative 

b.

 

Use wire nuts for connection (not supplied). 

7.

 

Connect Battery connectors to the panel (See Figures 4 and 6). 

8.

 

Adjust head(s) as follows: (See Figure 3). 

a.

 

Rotation – Loosen head nut and rotate head to desired position. Retighten head nut. An antirotation screw has been 
provided to ensure proper rotation. 

b.

 

Angle – Loosen thumb screw passing through head swivel sufficiently to allow internal teeth to disengage. Position 
head to desired angle.  

c.

 

Retighten both head nut and thumb screw. 

CAUTION

 – 

ensure lamp heads are positioned so they are aimed below horizontal

 

9.

 

A dual load terminal block is provided for lamp hook-up. Ensure total wattage of heads, both unit mounted and remote (if 
applicable), does not exceed unit rating. Factory mounted lamps are wired to the terminal block at points L+ and L-. All 
remote loads should be wired to the terminal block at RL+ and RL- (See Figure 5). Use wire gauge that limits voltage drop to 
an acceptable level (See page 6). 

10.

 

Chevron labels with self-adhesive backing are supplied.  Apply label(s) to exit lens as necessary. 

11.

 

Remount exit lens using lens screws. Close cover and secure with cover screws. 

Содержание HZ Series

Страница 1: ...d metal hardware to the enclosure Do not store or place flammable materials near lamp Install only grounded wiring systems to supply this equipment CAUTION ensure lamp heads are positioned so they are aimed below horizontal CLASS I DIV 2 HAZARDOUS LOCATION GROUPS A B C AND D ZONE 2 GROUPS IIC IIB AND IIA CLASS II DIV 2 GROUPS F AND G AND CLASS III DIV 1 AND 2 INSTALLATION AND OPERATING INSTRUCTION...

Страница 2: ...r is used a Connect WHITE wire to 24VDC Positive and 24VDC Negative b Use wire nuts for connection not supplied 7 Connect Battery connectors to the panel See Figures 4 and 6 8 Adjust head s as follows See Figure 3 a Rotation Loosen head nut and rotate head to desired position Retighten head nut An antirotation screw has been provided to ensure proper rotation b Angle Loosen thumb screw passing thr...

Страница 3: ...hone 855 486 2216 www chloride lighting com Signify Canada Ltd Signify Canada Ltée 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 INSTRUCTIONS OPERATION 1 Energize AC power to exit Unit will initiate normal power up sequence See page 4 Figure 3 Battery Connectors Figure 4 Figure 5 Figure 6 ...

Страница 4: ...ating condition Rapid Flash product performing an automatic or manually initiated diagnostic test Red LED indicator Single Flash battery fault Two Flashes lamp failure light bar failure EXIT signs Three Flashes charger fault Four Flashes transfer fault If more than one fault condition is present simultaneously the red LED will flash the indication pattern for each fault independently then repeat t...

Страница 5: ...hone 855 486 2216 www chloride lighting com Signify Canada Ltd Signify Canada Ltée 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 IR Remote Control optional is a hand held device that allows remote activation of diagnostic testing and silencing of the optional buzzer during fault conditions ...

Страница 6: ... VOLTAGE DROP 5 CM L X 22 USING THE ABOVE FORMULA AND HAVING CALCULATED THE CIRCULAR MILLS REQUIRED TO CARRY THE SPECIFIED LOAD AT A PREDETERMINED AND ALLOWABLE VOLTAGE DROP THE FOLLOWING CHART WILL IDENTIFY THE NECESSARY WIRE GAUGE FROM THE CORRESPONDING CIRCULAR MILL SIZE LISTED WIRE GAUGE AMPERE CAPACITY OHMS PER 1000 ft CIRCULAR MILL SIZE 12 20 1 586 6 530 10 25 9972 10 380 8 35 6271 16 510 6 ...

Страница 7: ... North America Corporation 200 Franklin Square Drive Somerset NJ 08873 USA Phone 855 486 2216 www chloride lighting com Signify Canada Ltd Signify Canada Ltée 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 Figure 7 ...

Страница 8: ...one 855 486 2216 www chloride lighting com Signify Canada Ltd Signify Canada Ltée 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 Top Assembly Drawing For Reference only Heads Batteries Chassis assembly Lens Figure 8 Batteries Control Board Membrane switch Chassis assembly back view Figure 9 ...

Отзывы: