![Chloride ACTIVE 1000-19 Скачать руководство пользователя страница 27](http://html.mh-extra.com/html/chloride/active-1000-19/active-1000-19_operating-manual_2602759027.webp)
CHLORIDE ACTIVE
Installation and commissioning
945040.066
V02OCT/01
GB - 23
G
B
Notice
On delivery, the nominal voltage of the UPS devices is 230 V. Using
software, the output voltage of the UPS can be set to other values
(see Table 7 on page GB - 39). The required software can be down-
loaded from the CHLORIDE Internet page (http://www.chloridepow-
er.com).
Commissioning of an external battery extension
The table below contains an overview of the designations of the battery
extensions available for the UPS devices.
Upright devices: A maximum of two battery extensions may be connected
to a UPS device.
Rack-mounting devices: A maximum of two battery extensions may be
connected to the ACTIVE 1000-19 UPS device and five battery extensions
to the ACTIVE 2000-19 and ACTIVE 3000-19 UPS devices.
Danger
Make certain that the circuit breaker on the battery extension is in the
"OFF" position.
For models ACTIVE 1000(-19) to ACTIVE 3000(-19), connect the battery extension to
the UPS using the supplied cable.
The arrangement of the connection cable is shown in the following figures
using the upright device as an example.
UPS model
Battery extension model Battery used
Maximum number which
may be connected
ACTIVE 700
not possible
ACTIVE 1000
BPACTIVE1000
2 x (3 x 7.0 Ah)
2 pieces
ACTIVE 2000
BPACTIVE3000
2 x (8 x 7.0 Ah)
2 pieces
ACTIVE 3000
BPACTIVE3000
2 x (8 x 7.0 Ah)
2 pieces
ACTIVE 700-19
not possible
ACTIVE 1000-19 BPACTIVE1000-19
2 x (3 x 7.0 Ah)
2 pieces
ACTIVE 2000-19 BPACTIVE2000-19
1 x (8 x 7.0 Ah)
5 pieces
ACTIVE 3000-19 BPACTIVE3000-19
1 x (8 x 7.0 Ah)
5 pieces
Table 5: Battery extensions (maximum expansion)
Содержание ACTIVE 1000-19
Страница 2: ......
Страница 52: ...Technical data CHLORIDE ACTIVE GB 48 V02OCT 01 945040 066 ...
Страница 59: ...MASTERGUARD ...