4.2
Client Side Connection Descriptions
Create one connection for each CHC. Each connection can only be used to connect to a single CHC interface.
SECTION TITLE
Connections
COLUMN TITLE
FUNCTION
LEGAL VALUES
Port
Specify which port the device is
connected to the FieldServer
P1-P8, R1-R2
1
Protocol
Specify protocol used
FSU_ESC
Baud*
Specify baud rate
Driver Supports : 110; 300; 600;
1200; 2400; 4800;
9600
; 19200;
28800; 38400; 57600; 115200 Baud
Vendor Equipment Supports : 1200
Baud
Parity*
Specify parity
Driver Supports : Odd, Even,
None
Vendor Equipment Supports:
None
Data_Bits*
Specify data bits
Driver Supports : 7,
8
Vendor Equipment Supports : 8
Stop_Bits*
Specify stop bits
Driver Supports : 1,2
Vendor Equipment Supports: 1
Handshaking*
Specify hardware handshaking
None
Poll _Delay*
Time between internal polls
0-32000 seconds,
0.2 second
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports
available on specific hardware.