Environmental conditions

Ambient temp. (℃)

Hot and humid 

atmospheric conditions

-

5℃

40℃, average temperature should not 

35℃ within 24h

~+

Relative humidity should not exceed 50% at 
+40℃; up to 90% at +20℃;

Pollution class/installation category

Altitude

No influence below 2000m,

Class 3/

Main technical parameters

The Purpose of Use

1

NS2-80B AC motor starter is applicable to circuits with frequency of AC 

50Hz or 60Hz, rated operating voltage up to 415V and current up to 80A. It 
is  used  for  infrequent  start  control  of  3-phase  squirrel  cage  asynchronous 
motor  and  it  can  protect  motor  from  short  circuit,  overload  and  loss  of 
phase.  The  product  can  also  be  used  for  distribution  line  protection  and 
infrequent load transfer or used as isolator. 

NS2-80B  AC  motor  starter  can  be  added  with  a  set  of  side  mounted 

auxiliary  contacts:  AU11(1NO+1NC)  or  AU20(2NO).  See  product  catalog  or 
product itself for technical parameters of auxiliary contacts.

Main Technical Parameters

2

Table 1 Main technical parameters

No

Frame 

size 

rated 

current 

I

nm 

A

Release 

rated 

current 

I

n  

A

Adjustment 

range of 

thermal 

element 

setting

 current 

A

Release 

setting 
current

 value for

 short 
circuit

 current

I

r

 A

Rated ultimate short 

circuit breaking capacity 

I

cu

, Rated operating 

short circuit breaking 

capacity I

cs

 kA

Arcing 

distance 

mm

400/415V

1

2

3

4

80

50

25

40

63

80

16-25

25-40

40-63

56-80

350

560

882

1120

I

cu

15

15

15

15

I

cs

7.5

7.5

7.5

7.5

Содержание NS2-80B

Страница 1: ...NO 2020 04 Standard IEC EN 60947 2 IEC EN 60947 4 1 NS2 80B AC Motor Starter User Instruction ...

Страница 2: ...llation in any damp condensed phase environment with inflammable and explosive gas is forbidden When the product is being installed or maintained the power must be switched off You are prohibited from touching the conductive part when the product is operating 1 2 3 4 Safety Warning ...

Страница 3: ...oad and loss of phase The product can also be used for distribution line protection and infrequent load transfer or used as isolator NS2 80B AC motor starter can be added with a set of side mounted auxiliary contacts AU11 1NO 1NC or AU20 2NO See product catalog or product itself for technical parameters of auxiliary contacts Main Technical Parameters 2 Table 1 Main technical parameters No Frame si...

Страница 4: ...nducting bar strip length before being inserted into terminal mm Conductor wire conducting bar 2 sectional area mm Allowable maximum number of conductor wire conducting bar to be inserted Size of fixing screws or bolts at wiring end Tightening torque for fixing screws at wiring end N m Operation frequency times hour 690V 400 415 50 60Hz 6kV IP20 Long term duty system 15 4 25 2 M8 6 25 No Parameter...

Страница 5: ...ng current Time s 10000 1000 100 10 1 0 1 0 01 0 001 1 1 2 2 3 3 1 1 5 2 10 100 1 Start from cold state 3 pole 2 Start from cold state 2 pole 3 Start from thermal state 3 pole Figure 1 Time current characteristic curve 20 ...

Страница 6: ...0A 68 56 80 Figure 2 Overall and installation dimensions of NS2 80B See Figure 3 for assembly procedure of starter and auxiliary contacts when the starter is disconnected a Confirm the starter is disconnected the red OFF button is press down b Hang the front end of the auxiliary contacts on the slot at the left front of the starter and move the auxiliary contacts towards the starter ...

Страница 7: ...nd hold the blue button at the end of the auxiliary contacts and fit it into the starter e After fitting the auxiliary contacts break and make the starter for 5 10 times check if the slot at the center of the auxiliary contacts can move together with the starter reliably In the meantime check if the auxiliary contacts are powered on normally if there is any abnormality repeat step a step d a b c d...

Страница 8: ...tarter is within its setting current range 3 3 3 Check if the starter can operate smoothly press down the green button of the starter or turn the knob to ON position flip the guide plate beside the TEST mark on the cover according to the direction shown by the arrow You can hear the operation sound of the contact and the green button will bounce back or the knob will be turned to OFF position Repl...

Страница 9: ...15 315 315 315 400 400 No Rated current In A Rated operating current adjustment range of thermal element setting current Melt current backup fuse is only needed when Isc Icu 400 415V aM A gL gG a Maintenance 4 Clean the dust on the motor starter timely Conduct product test and maintenance every half a year to ensure the smooth operation of the product and the good contact of NO and NC contacts Tig...

Страница 10: ...operating current of the motor Strong shock or vibration Fine tune the cam to match the set current matches the actual motor current Check installation status and conduct troubleshooting Do not place the product in environment with strong shock or vibration Frequent start of motor The start frequency of the motor should not exceed 25 times per hour The sectional area of the connecting wire is too ...

Страница 11: ...QC PASS Test date Please see the packing ZHEJIANG CHINT ELECTRICS CO LTD NS2 80B AC Motor Starter IEC EN 60947 2 IEC EN 60947 4 1 Check 28 09 ...

Страница 12: ...C Motor Starter User Instruction Zhejiang Chint Electrics Co Ltd Add No 1 CHINT Road CHINT Industrial Zone North Baixiang Yueqing Zhejiang 325603 P R China E mail global sales chint com Website http en chint com ...

Отзывы: