10
Environmental Protection
5
In order to protect the environment, the product or product parts
should be disposed of according to the industrial waste treatment process,
or be sent to the recycling station for assortment, dismantling and recycling
according to local regulations.
Table 9 Analysis and Troubleshooting of Faults
Symptoms
Cause analysis
Troubleshooting method and precautions
The starter
operates in
advance.
The starter
does not
operate.
The setting current of the
starter is smaller than the
actual operating current
of the motor.
Strong impact or
vibration
Use the cam to fine tune the product to
match the setting current matches with the
actual current of the motor.
Check the installation site and eliminate the
fault to match the product is free from
strong impact or vibration.
Frequent start of motor
There should be a certain interval between
each start of the motor. The maximum start
frequency is 25 times/hour.
The cross-sectional area
of the connecting wire is
too small.
Select standard wire according to Table 7.
The setting current of the
starter is bigger than the
rated current of the
motor.
Use the cam to fine tune the product to
match the setting current matches with the
actual current of the motor.
The cross-sectional area
of the connecting wire is
too big.
Select standard wire according to Table 7.