background image

06

3.3

  Test/reset  button  instructions:  “TEST/RST”  on  the  protector  is  the 

test/reset  button.  Press  it  when  the  product  is  working  normally,  the 
protector  motions  and  the  red  light  flashes;  press  it  after  a  fault,  the 
protector is reset.

3.4

  Adjustment  of  the  setting  current  value:  the  protector  uses  the  setting 

knobs  with  indicating  arrows.  Based  on  the  setting  current  value  on  the 
nameplate,  set  the  current  according  to  the  rated  current  and  motor  load 
condition marked on the nameplate of the motor. Adjust the setting current 
value of the protector to a scale equal to the rated current value marked on 
the motor nameplate.

3.5

 Commissioning: After confirming that the wiring and setting are correct, 

power on the product and press the start button, then the motor should be 
able  to  run  normally  and  the  (green)  operation  indicator  on  the  panel 
should  be  on.  If  the  red  indicator  flashes,  fine  tune  the  setting  value  until 
the red indicator light just does not flash.

Notes: 

1 Check the performance of the protector on a regular basis. Perform overload 
and  loss  of  phase  testing.  The  testing  should  be  performed  by  professional 
technicians to ensure the safety of electricity use.

2

The  setting  error  of  the  protector  shall  not  be  greater  than  5%.  When  the 

current of the main circuit is within this range, the overload indicator may be on.

3

If the motor stops during its operation, the motor should be checked for loss 

of  phase  or  overload.  First,  check  whether  the  temperature  rise  of  the  motor  is 
too  high.  If  the  temperature  rise  is  too  high,  the  stop  may  be  caused  by 
overload; if not, the motion of the protector may be caused by the loss of phase 
of  the  circuit.  Check  whether  the  three-phase  power  supply  is  normal,  whether 
the  dynamic  and  static  contacts  of  the  AC  contactor  are  in  good  contact,  and 
whether  the  three-phase  power  line  of  the  motor  has  loosened;  if  everything 
goes well but the motor still cannot be started, then carefully check whether the 
self-locking contact of the AC contactor and the terminal wiring of the protector 
have loosened. The motor cannot be started until the fault is eliminated. When 
the fault is not eliminated, it cannot be started forcibly for fear of accidents.

4

Do  not  open  the  protector  without  permission,  so  as  to  avoid  danger  or 

affecting the normal operation of the protector.

Содержание NJBK6 Series

Страница 1: ...NO 2020 09 Standard IEC EN 60947 4 1 NJBK6 Series Motor Protector User Instruction ...

Страница 2: ...s forbidden When the product is being installed or maintained the power must be switched off You are prohibited from touching the conductive part when the product is operating The product shall be stored installed and used in accordance with the rated control power supply voltage and specified conditions indicated in the user instructions 1 2 3 4 5 Safety Warning ...

Страница 3: ...not exceed 50 when maximum temperature is 40 in case of lower temperature higher RH is allowed Measures should be taken against occasional condensation due to temperature change Ⅲ 25 55 Table 2 Product Specifications and Main Technical Parameters Model Setting current A Current setting range A Motor power kW NJBK6 36 3 NJBK6 36 9 NJBK6 36 24 NJBK6 36 36 3 1 3 0 5 1 5 9 3 9 1 5 4 5 24 8 24 4 12 36 ...

Страница 4: ...Rated control supply voltage Us V frequency Hz Allowable fluctuation range of rated control power supply voltage Rated impulse withstand voltage Uimp kV Rated conditional short circuit current kA CPD type SCPD model Contactor model CJX2 25 NC1 25 Enclosure protection class if applicable IP20 M3 0 5 Size of terminal tightening screw or nut Torque of terminal tightening screw N m Class 3 8h duty or ...

Страница 5: ...1 Motion characteristic 2 1 1 See Table 5 for the motion characteristic of overload protection Table 5 Motion Characteristic of Overload Protection Setting current multiple 1 05 1 2 1 5 7 2 Cold Thermal Cold Starting condition Ambient air temperature 20 2 1 2 Motion characteristic of phase loss protection When any one of the three phase currents of the main circuit is open the protector motions fo...

Страница 6: ... The blocking current set in the protector is 6Ie When the current of the main circuit is greater than the blocking current the protector motions for 3s with a delay and a relative error of 20 2 2 Reset characteristic i I avg I After the protector motions the protector s reset mode is manual reset when the rated control power supply voltage is normal the protector is immediately reset when the rat...

Страница 7: ... FU1 W1 V1 U1 QS FU2 W2 V2 U2 W3 V3 U3 W4 V4 U4 QF1 KM KM STP ST QF1 KM 95 96 A1 A2 M 3 Figure 2 Wiring Diagram of the Protector with the Control Power Supply Voltage of AC220V AC240V 05 3 2 Wiring diagram See Fig 2 Fig 3 Figure 3 Wiring Diagram of the Protector with the Control Power Supply Voltage of AC380V ...

Страница 8: ... of phase testing The testing should be performed by professional technicians to ensure the safety of electricity use 2 The setting error of the protector shall not be greater than 5 When the current of the main circuit is within this range the overload indicator may be on 3 If the motor stops during its operation the motor should be checked for loss of phase or overload First check whether the te...

Страница 9: ...e environment the product or product parts should be disposed of according to the industrial waste treatment process or be sent to the recycling station for assortment dismantling and recycling according to local regulations 4 1 The terminal of the protector should be tightened on a regular basis 4 2 Avoid squeezing the product the product should be stored in a well ventilated place Connect wires ...

Страница 10: ...QC PASS Test date Please see the packing ZHEJIANG CHINT ELECTRICS CO LTD NJBK6 Series Motor Protector IEC EN 60947 4 1 JDQ Check 10 09 ...

Страница 11: ...s Motor Protector User Instruction Zhejiang Chint Electrics Co Ltd Add No 1 CHINT Road CHINT Industrial Zone North Baixiang Yueqing Zhejiang 325603 P R China E mail global sales chint com Website http en chint com ...

Отзывы: