P2 Low pressure
protection
Flash’s 9
times
1.
Low pressure switch
loose or faulty.
2.
Throttling device
(expansion valve)
problem
3.
Heat expansion valve
needs to be
preheated.
4.
Refrigerant low
(leaks)
1.
If the error displays before the
compressor starts, it means
low pressure switch error.
Please reconnect the low
pressure switch or change it.
2.
Open the thermostatic
expansion valve 360~180°.
3.
Disconnect the power for 3
minutes, connect power again
and turn on the unit. Repeat
this 2 or 3 times to preheat
the expansion valve.
4.
Check for refrigerant leakage.
P5
indoor unit
water flow
fault
No flash
1.
Low water flow.
2.
Water flow switch
fault.
1.
Clean the water filter, check
water pump flow.
2.
Check and reconnect water flow
switch.
P6
outdoor unit
(water source
side) water
flow fault
Flash’s
17
times
1.
Water source side
water flow too small.
2.
Water flow switch
fault.
1.
Clean the water filter, check
water pump flow. Test the
water flow switch.
P7 phase loss
Flash
Power connection fault
Reconnect power supply wires
P8
Flash
Power connection fault
Reconnect power supply wires
P9
Flash
Power supply connection
fault or communication
between indoor and
outdoor PCB fault
1.
Check the power supply
wire connection and wires
between outdoor PCB and
indoor PCB.
2.
Check if the outdoor PCB
has an error.
Содержание CX45
Страница 4: ...4...
Страница 9: ...9 Freeze protection...
Страница 10: ...10...
Страница 11: ...11...
Страница 12: ...12...
Страница 13: ...13...
Страница 14: ...14...
Страница 15: ...15...
Страница 16: ...16...
Страница 17: ...17...
Страница 18: ...18...
Страница 19: ...19...
Страница 20: ...20...
Страница 21: ...21...
Страница 22: ...22...
Страница 23: ...23...
Страница 24: ...24...
Страница 33: ...33 Clearances unit mm 200mm 8 350mm 14 400 16 500 20 1000 40...
Страница 36: ...36 Second PWM Pump Wiring Use proper splicing connectors to connect the second PWM pump in parallel to CN6...
Страница 39: ...39 G3 VALVE Seasonal Switch Valve Solar Pre heat Valve...
Страница 40: ...40 G1 Valve DHW and AC...