54
ERROR CODES
When the machine has an error, the control will show “P” or “E” at the AC temp location and show
the error code at the DHW temp location, press key
to search more error codes that may have
happened at the same time. Please see table below for error code meaning.
Error code list
Error
Code
Error Meaning
Outdoor
Led2
Possible Error
Reason
Error Solution
E1
Compressor
discharge gas
high temp.
protection
Flash’s
10 times
1.
Refrigerant low
2.
throttling device
problem
3.
Water flow volume
is too low
1. Check the refrigerant
pressure and check if there is
leakage.
2. Check the thermostatic
expansion valve.
3. Check the water flow volume
and if the water pump is too
small or is blocked.
E2
Outdoor air temp
sensor fault
Flash’s
3 times
Sensor open circuit or
short circuit
1. Reconnect the sensor
2. Measure the sensor
resistance at different
temperatures, if it is out of
range change the sensor.
E3
Pipe temp or
returned air temp
sensor fault
Flash’s
6 times
Sensor open circuit or
short circuit
1.
Reconnect the sensor
2.
Measure the sensor
resistance at different
temperatures, if it is out of
range change the sensor.
E4
AC returned water
temp. sensor fault
No flash
Sensor open circuit or
short circuit stop
compressor in AC
1.
Reconnect the sensor
2.
Measure the sensor
resistance at different
temperatures, if it is out of
range change the sensor.
E5
AC output water
temp. sensor fault
No
flash
Sensor open circuit or
short circuit stop
compressor in AC
1.
Reconnect the sensor
Measure the sensor
resistance at different
temperatures, if it is out of
range change the sensor.
Содержание CX45
Страница 4: ...4...
Страница 9: ...9 Freeze protection...
Страница 10: ...10...
Страница 11: ...11...
Страница 12: ...12...
Страница 13: ...13...
Страница 14: ...14...
Страница 15: ...15...
Страница 16: ...16...
Страница 17: ...17...
Страница 18: ...18...
Страница 19: ...19...
Страница 20: ...20...
Страница 21: ...21...
Страница 22: ...22...
Страница 23: ...23...
Страница 24: ...24...
Страница 33: ...33 Clearances unit mm 200mm 8 350mm 14 400 16 500 20 1000 40...
Страница 36: ...36 Second PWM Pump Wiring Use proper splicing connectors to connect the second PWM pump in parallel to CN6...
Страница 39: ...39 G3 VALVE Seasonal Switch Valve Solar Pre heat Valve...
Страница 40: ...40 G1 Valve DHW and AC...