Chiltrix Inc.
Setting the target or Set Point Temperature
Next, to set the temperature, go back to the desktop and touch the “set target AC” icon. Using the
keypad select the desired temperature and touch the “ENT” icon.
Note* The AC Target must be set for both heating and cooling modes. The target temperature is
the EWT (entering water temperature) (return temperature) and implies a LWT (leaving water
temperature)(supply temperature) 9-10F higher. For example , for heating target if you want a
supply temperature of 100F set the AC Target to 90F. For a cooling supply temp of 44F, the AC
target would be 54F