Prior to installation and commissioning of the chiller, please observe the following points strictly:
The fresh air intake temperature may not exceed the max.ambient temperature
(refer to name plate)
Assure that the required quantity of air is available at air cooled chillers.
Assure that the chiller hot air outlet does not warm up the environment or room excessivly
.
Min.distance of fresh air intake:
at least 0,5 m (air cooled version)
Min.distance of hot air outlet:
at least 1,0 m (air cooled version)
Connection of an air supply and exhaust duct is not admitted.
The fresh air intake of the unit (condensor) may not be situated infront of a heat rejecting
device like a pump or electric motor.
The unit must be set up on level, solid surfaces only, in order to ensure the required stability.
For outside erected chillers, the minimum outdoor temperature should be considered from the
technical data.
Floor space
A minimum space must be left open around the installation, so that there is access to the various components and
to the control cabinet.
The distance from any constructions blocking the air supply must be at a minimum
distance of 0,5 meter.
3
INSTALLATION AND INITIAL OPERATION
According to EN 60204-1 the chiller must be positioned in a way that its power switch is located
at a height between 0.6m-1.9m above the access level (floor).