![Chigo CCB-18HVR4 Скачать руководство пользователя страница 147](http://html1.mh-extra.com/html/chigo/ccb-18hvr4/ccb-18hvr4_technical-manual_2601244147.webp)
R3250Hz Universal Outdoor Series Technical Manual
143
GD Chigo Heating & Ventilation Equipment Co., Ltd.
5 Insulation Work
5.1 Insulation material and thickness
5.1.1. Insulation material
Insulation material should adopt the material which is able to endure the pipe’s temperature: no
less than 70
℃
in the high-pressure side, no less than 120
℃
in the low-pressure side(For the cooling type
machine, no requirements at the low-pressure side.)
Example: Heat pump type----Heat-resistant Polyethylene foam (withstand above
120
℃
)
Cooling only type----Polyethylene foam (withstand above 100
℃
)
5.1.2. Thickness choice for insulation material
Insulation material thickness is as follows:
Pipe diameter (mm)
Adiabatic material thickness
Refrigerant pipe
Φ6.4
—
Φ25.4
10mm
Φ28.6
—
Φ38.1
15mm
Drainage pipe
Inner diameter
Φ20
—
Φ32
6mm
5.2 Refrigerant pipe insulation
5.2.1. Work Procedure
①
Before laying the pipes, the non-jointing parts and non-connection parts should be heat
insulated.
②
When the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat
insulated
5.2.2. Insulation for non-jointing parts and non-connection parts
wrong
right
Gas pipe and liquid pipe should
not be put together to insulate
Insulate the gas pipe
(cooling only)
Insulate the gas pipe and
liquid pipe
Содержание CCB-18HVR4
Страница 48: ...R3250Hz Universal Outdoor Series Technical Manual 44 GD Chigo Heating Ventilation Equipment Co Ltd...
Страница 93: ...R3250Hz Universal Series Technical Manual 89 GD Chigo Heating Ventilation Equipment Co Ltd 4 Service Space...
Страница 116: ...R3250Hz Universal Series Technical Manual 112 GD Chigo Heating Ventilation Equipment Co Ltd 2 4 COU 48HZDR4 COU 60HZVR...
Страница 117: ...R3250Hz Universal Series Technical Manual 113 GD Chigo Heating Ventilation Equipment Co Ltd 3 Service Space...
Страница 127: ...R3250Hz Universal Outdoor Series Technical Manual 123 GD Chigo Heating Ventilation Equipment Co Ltd 8 2 COU 24HDR4...
Страница 129: ...R3250Hz Universal Outdoor Series Technical Manual 125 GD Chigo Heating Ventilation Equipment Co Ltd 8 3 COU 36HDR4...
Страница 131: ...R3250Hz Universal Outdoor Series Technical Manual 127 GD Chigo Heating Ventilation Equipment Co Ltd 8 4 COU 36HZDR4...
Страница 159: ...R3250Hz Universal Outdoor Series Technical Manual 155 GD Chigo Heating Ventilation Equipment Co Ltd...