R3250Hz Universal Outdoor Series Technical Manual
140
GD Chigo Heating & Ventilation Equipment Co., Ltd.
4 Water Drainage
4.1 Gradient and Supporting
4.1.1 Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as
short as possible and eliminate the air bubble.
4.1.2 The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be
installed to keep the gradient of 1/100 and prevent bending. Refer to the following table for the specification
of the prop stand.
Diameter
Distance between the prop stands
Hard PVC pipe
25~40mm
1~1.5m
4.1.3. Precautions
①
The diameter of drainpipe should meet the drainage requirement at least.
②
The drainpipe should be heat-insulated to prevent atomization.
③
Drainpipe should be installed before installing indoor unit. After powering on, there is some water in
water-receiver plate. Please check if the drain pump can operate correctly.
④
All connection should be firm.
⑤
Wipe color on PVC pipe to note connection.
⑥
Climbing, horizontal and bending conditions are prohibited.
⑦
The dimension of drainpipe can’t less than the connecting dimension of indoor drainpipe.
⑧
Heat-insulation should be done well to prevent condensation.
⑨
Indoor units with different drainage type can’t share one convergent drainpipe.
4.2 Drainpipe Trap
4.2.1. If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe
trap.
4.2.2. Every indoor unit needs one drainpipe trap.
4.2.3. A plug should be designed to do cleaning.
Plug
5
0
cm
5
0
c
m
Содержание CCB-18HVR4
Страница 48: ...R3250Hz Universal Outdoor Series Technical Manual 44 GD Chigo Heating Ventilation Equipment Co Ltd...
Страница 93: ...R3250Hz Universal Series Technical Manual 89 GD Chigo Heating Ventilation Equipment Co Ltd 4 Service Space...
Страница 116: ...R3250Hz Universal Series Technical Manual 112 GD Chigo Heating Ventilation Equipment Co Ltd 2 4 COU 48HZDR4 COU 60HZVR...
Страница 117: ...R3250Hz Universal Series Technical Manual 113 GD Chigo Heating Ventilation Equipment Co Ltd 3 Service Space...
Страница 127: ...R3250Hz Universal Outdoor Series Technical Manual 123 GD Chigo Heating Ventilation Equipment Co Ltd 8 2 COU 24HDR4...
Страница 129: ...R3250Hz Universal Outdoor Series Technical Manual 125 GD Chigo Heating Ventilation Equipment Co Ltd 8 3 COU 36HDR4...
Страница 131: ...R3250Hz Universal Outdoor Series Technical Manual 127 GD Chigo Heating Ventilation Equipment Co Ltd 8 4 COU 36HZDR4...
Страница 159: ...R3250Hz Universal Outdoor Series Technical Manual 155 GD Chigo Heating Ventilation Equipment Co Ltd...