TROUBLE
TROUBLE
TROUBLE
TROUBLE SHOOTING
SHOOTING
SHOOTING
SHOOTING
nd other components on the electric
control board have damaged, replace
the controllable silicon or electric control
board when they are damaged.
E6
PG motor
display at
off state
flicker 6/8
SEC
display
at off
state
no over zero
signal
1
、
Firstly check whether the indoor fan is
normal.
2
、
Check whether the signal outputting from
the integrated chip of the electric control
board is normal, the electric control
board should be replaced when the
signal is abnormal.
E7
display at
off state
flicker 7/9
SEC
display
at off
state
outdoor
feedback fault
1
、
Check whether the winding resistance
and operation current of the compressor
are normal
2
、
Check whether the high and low pressure
is normal when the unit is running.
3
、
Check whether the indoor and outdoor
wiring is right; when it is wrong, connect
them again according to the circuit
diagram
4
、
Check whether the contact of the
inserter on the circuit board and the
connection are well, otherwise
repair.
5
、
Check whether the signal feedback wire
is disconnected, replace or connect the
feedback signal wire.
6
、
Check whether the supply power is
phase-lacking or phase opposition.
7
、
Check whether the AC electromagnetic
contactor is well.
E8
display at
off state
flicker 8/10
SEC
display
at off
state
frost
protection/over
heat protection
1
、
Check whether the filter of the indoor
unit is dirty or blocked, and clean if it is
dirty.
2
、
Check whether the indoor fan is running
normally, and replace the motor if it is
abnormal.
3
、
Check whether indoor pipe temperature
sensor is normal, and replace the sensor
if it is abnormal.
4
、
Check whether the system pressure is
normal,
if
abnormal,
should
check
whether there is leakage, and fill the
refrigerant again.