Installation Instructions
EGX-SF2
9
Using New Work Clip
NOTE:
This installation is only recommending if installing to a
new work site where the drywall has not been installed
yet.
1.
Remove outlet box from housing following Steps 1-3 in the
"Installing EGX-SF2" Section.
2.
Locate desired mounting location next to a wood or steel
stud.
3.
Use two #12-24 x 3/8" Phillips tapping screws (F) to secure
new work clip (E) to outside of outlet box (A). (See Figure
10)
Figure 10
4.
Install to stud using mounting holes in new work clip (E) and
appropriate hardware depending on type of stud.
NOTE:
Refer to marks on the side of the outlet box to attach
work clip at the right location based on the thickness of
the drywall to be installed.
5.
Route wires from electrical conduit through knockout hole
per local building code. Use wire nuts to safely terminate
wires until drywall is installed. (See Figure 11)
Figure 11
6.
Install drywall around outlet box. Cut an opening around the
box meeting the dimensions shown in Figure 11 next to the
stud used to attach new work clip. (See Figure 12)
NOTE:
Notch appropriate side of drywall to accommodate the
old work clip (C).
Figure 12
7.
Connect wires to EGX-SF2 referring to tables on page 3 for
input and output specifications. (See Figure 3)
CAUTION:
Isolated ground-mounting means NOT
grounded. Grounding wire connection required.
IMPORTANT ! :
If a separate isolated green/yellow
ground wire is installed in the building wiring, attach it
separately to the green/yellow isolated ground wire on
box. If there is no separate green/yellow isolated ground
wire, connect green ground wire to both green/yellow
isolated ground wire and green box ground wire on box.
NOTE:
The grounding conductors serving this outlet are to be
connected to earth ground at the service equipment or
other acceptable building earth ground such as the
building frame in the case of a high-rise steel-frame
structure. Connections should be made with minimum
AWG 14 copper wire intended for use on a 15 Amp
circuit. The conductors used to connect the outlet to the
line and to ground shall not be any longer than
necessary and shall avoid unnecessary bends.
NOTE:
An insulated grounding conductor that is identical in
size and insulation material and thickness to the
grounded and ungrounded circuit supply conductors,
except that it is green with or without one or more
yellow stripes, is to be installed as part of the circuit that
supplies the outlet. Refer to Table 250-122 of the
National Electrical Code regarding the appropriate size
of the grounding conductor.
NOTE:
Pressure terminal or pressure splicing connectors and
soldering lugs used in the installation of the outlet shall
be identified as being suitable for the material of the
conductors. Conductors of dissimilar metals shall not
be intermixed in a terminal or splicing connector where
physical contact occurs between dissimilar conductors
unless the device is identified for the purpose and
conditions of use.
(F) x 2
3
(E)
(A)
5
conduit
EGX-SF2
4-1/4” MAX
(108 mm)
4” MAX
(101.6 mm)
CUTOUT AREA