background image

FAN BEARINGS:

1. Lubricate fan bearings per bearing manufacturer’s instructions in the

packet attached to the fan. The fan is shipped with premium quality
lithium based NLGI #2 grade grease. Continue to use NLGI #2 unless
the  bearing  manufacturer’s  instructions  specify  a  different  type  of
grease  for  your  application.  Lubricate  bearings  immediately  upon
receipt.  Add  enough  grease  to  cause  slight  purge  at  seals.  It  is 
common for bearings to purge excessive grease during first 24 to 48
hours of operation. See bearing manufacturer’s instructions enclosed
for lubrication schedule.

2. Bearing must be properly locked to the shaft. Check before operation.

Make sure bearing locking collar is in position and set screws are tightened
to the bearing manufacturer’s recommended torque levels. See bearing
manufacturer’s instructions enclosed for details. The bearing set screws
should be re-torqued after eight and twenty-four hours of operation.

VERTICALOPERATION:

If the fan is to operate with its shaft vertical, reset the bearings as 
follows

a.  With  the  shaft  vertical,  unlock  the  drive  end  bearing  set  screws 

and turn the shaft by hand. This allows the wheel end bearing to     
take the gravity load of the shaft and wheel. 

b. Re-lock the drive end bearing locking device and replace and torque set  

screws  as  required  by  the  bearing  manufacturer’s  instructions  so  that 
this bearing now takes only the belt pull.

FANS WITH COUPLINGS:

On any completely assembled fan, where CBC has mounted the motor
and coupling, it is required that the alignment be rechecked after the fan
is set on its permanent foundation. It is not possible to hold alignment
during shipment or when set on a different foundation. Coupling must be
realigned and lubricated per manufacturer’s instructions sent with the fan.

V-BELT DRIVES:

1. Alignment of the drives must be checked with a straightedge or string.

Belt tension must must be properly adjusted to assure good belt and
bearing life. Sheave faces should be parallel and aligned within 1/16".

Use balanced sheaves.

2. With all belts in their proper grooves, adjust the centers to take up all

slack and until the belts are fairly taut.

3. It is normal on v-belt drives handling more than 20 HP to “squeal” on

start-up. 

Do not tighten belts too tight.

Normal belt tension can be

determined  by  being  able  to  depress  belt,  at  mid-point  a  distance
equal to one belt width, with normal finger pressure.

4. After a few days operation the belts will seat themselves in the sheave

grooves  and  it  may  become  necessary  to  readjust  so  that  the  drive
again shows a slight “bow” in the slack side. The drive is now properly
tensioned  and  should  operate  satisfactorily  with  only  an  occasional
readjustment to compensate for belt and groove wear.

OPERATION OF FAN:

After installing the fan per these instructions and the instructions of the
manufacturers, make final safety checks to prevent injury to personnel
or damage to the equipment. 

Always block rotating parts to prevent

windmilling while inspecting the fan.

1. Lock power source in “OFF” position.  

2. Check bearings for alignment and proper lubrication, with wheel and

inside of the housing clean and free of debris.

3. Check wheel position for proper clearance and rotation. Unblock rotat-

ing parts and turn wheel by hand to insure that it rotates freely.

4. Check sheave set screws or bushings and wheel set screws for tight-

ness. If fan is a HEAT FAN, check to see that the shaft cooling wheel
bolts  are  tight.  Check  foundation  bolts.  Secure  safety  guards  and
access doors.

5. If fan is designed for low density (such as high temp), make sure over-

load of fan motor is avoided if fan is run with standard air. 

6. Start fan and allow unit to reach full speed, then shut down. During

this short period, check for rotation, excessive vibration, any unusual
noise,  or  overheating  of  the  motor.  Check  the  motor  amps  drawn
against  the  nameplate  rating.  A  plate  over  the  fan  inlet  will  limit  the
horsepower drawn during a test run with limited ductwork.

7. After the trial run lock the power “OFF”.

8. Recheck for tightness of hold-down bolts, wheel set screws and keys,

and retighten if necessary. Recheck after eight and twenty-four hours
of operation.

9. The  run-in  period  should  be  at  least  eight  hours.  Check  bearings  a

minimum  of  once  each  hour  during  this  period.  Overgreasing  may
cause bearings to heat up. There need be no concern if the bare hand
can  be  held  on  the  bearings  briefly.  Bearings  will  vent  extra  grease 
and  cool  down  after  start-up.  Recheck  torque  of  all  bearing  set 
screws after eight and twenty-four hours of operation to insure levels
are maintained per the bearing manufacturer’s recommended levels.

Take  vibration  readings  at  the  bearings,  or  the  motor  bearings  if 
the fan wheel is mounted directly on the motor shaft. Adhere to these
limits.  Velocity  limits  in  inches/second  –  Normal:  0.15;  Alarm:  0.22;
Shutdown: 0.50

MAINTENANCE:

To insure long life and trouble-free service, frequently check all bearing
lubrication. See the bearing manufacturer’s instructions packed with the
fan. Should excessive vibration develop, check the following possibilities:

1. Build-up of dirt or foreign material on the wheel.

2. Loose bolts on bearings, housings, foundation and drive. 

3.  V-belt  drive  improperly  aligned.  Belts  must  have  proper  tension,

sheaves must be balanced.

4. Check wheel set screws.

5. Foreign matter may have entered fan causing damage to wheel, shaft

or bearings.

6. Vibration may be coming from a source other than the fan. Stop the fan

and determine if the vibration still exists. Disconnect the driver from the
fan and operate it by itself to determine if it produces vibration.

7. Proper clearance between the wheel and the inlet.

A preventive maintenance schedule is a necessity for extending fan life.
Establish  a  lubrication  schedule  based  on  time  periods  suggested  in
lubrication instructions and by motor and bearing manufacturers.

After approximately one (1) month of operation, all base, hub bearing,
pedestal, etc. bolts should be checked.

Potentially  damaging  conditions  are  often  signaled  in  advance  by
change in vibration and sound. A simple, regular audio-visual inspection
of  fan  operation  leads  to  correction  of  the  condition  before  expensive
damage occurs. Vibration levels should be check by an approved tech-
nician using electronic balancing equipment.

If air handled by the fan contains corrosive, erosive or sticky materials,
fan should be shut down regularly for inspection, cleaning and recondi-
tioning of interior parts.

If the fan is to remain idle for an extended period, fill bearing with grease.
Protect  motor  and  exposed  surfaces.  Follow  the  motor  manufacturer’s
recommendations for storage and rotate the shaft by hand several revo-
lutions each month.

Mechanical  Integrity:

Certain  operating  conditions  reduce  the  built-in

strength  in  the  fan  impeller  and  may  cause  unsafe  operation.  It  is  the
user’s responsibility to inspect for these conditions as frequently as nec-
essary and make corrections as required. Failure to comply with the fol-
lowing limits voids the Chicago Blower Corporation warrant.

Maximum  Safe  Speed  and Temperature: 

Operation  exceeding  maxi-

mum  safe  RPM  and  temperature  even  for  a  short  time  causes  over-
stressing or fatigue cracking of the impeller resulting in unsafe condition.
Maximum safe speed and maximum safe temperature are shown on fan
assembly drawings, catalogs or order acknowledgement.

(continued from previous page)

Warranty:

The warranty on Chicago Blower fans is our standard warranty. The warranty on the motor is that extended by the motor manufacturer.

10.

Отзывы: