Check engine mounts
Check crankcase ventilation system
Check condition of cooling fan assembly
Pressure test cooling system
Check engine electrical ground connection
Replace air filter element
Replace safety cartridge
Measure alternator insulation resistance (*)
Check glycol level in coolant
Check PH level of engine coolant
Check and adjust engine inlet and outlet valves
Check alternator and starter motor
Check electrical system for security of cables and wear
x
Test thermostats
x
Test glow plugs
x
Verify that safety circuits work
x
Inspection by Chicago Pneumatic Service technician
Generators in standby application have to be tested on a
regular basis. At least once a month the engine should run for
minimum 30 minutes at a high load ( 50% - 70% ) that the
engine reaches its operating temperature.
x
x
x
x
x
x
x
x
x
x
x
x
Содержание CPG 90-120 JD
Страница 1: ...CPG 90 120 JD Instruction Manual for AC Generators English ...
Страница 2: ......
Страница 19: ... 19 This is the described menu flow for changing the unit type ...
Страница 47: ... 47 Circuit diagrams ...
Страница 48: ... 48 1310 3200 01 00 Applicable for CPG 90 120 John Deere Power circuit ...
Страница 49: ... 49 ...
Страница 51: ... 51 ...
Страница 52: ... 52 1310 3200 00 00 Applicable for CPG 90 120 John Deere Engine circuit Qc1002TM ...
Страница 53: ... 53 ...
Страница 55: ... 55 ...
Страница 56: ...Printed in Belgium 04 2010 1310 3012 23 www cp com ...