17
7. Commissioning the Fire Unit
Turn on the gas supply
Check the gas supply and gas unit for soundness.
Light the appliance and check that all available functions work correctly. (See Lighting
the appliance’ in User Instructions for information).
Spillage checks
A spillage check must be done before the installed appliance is handed to the
customer.
The appliance must be fully fitted, all doors and windows closed in the room in which
the appliance is fitted. The appliance is to be tested after 5 minutes of the burn on
maximum position.
Light a smoke match and position flush with the fireplace opening testing around the
opening a minimum of 50mm from the sides and a maximum of 50mm from the top.
If the chimney is functioning correctly all smoke should be drawn into the chimney
and out of the room.
If this does not happen, check after a further 5 minutes of burn time on high rate. If
the smoke still does not expel all fumes then the unit is to be disconnected and expert
advice taken.
50mm
50mm
50mm