41
OPERATION OF CENTRALIZED COMMANDS
The module can be controlled centrally by means of a switch connected with the CENTR CMD terminals
of the J3 connector of the control unit through three wires (up, down, common) and by bringing the
switch to a level parallel to all the boards one wishes to control. Otherwise it is possible to centralize
modules in a sequence using the CHERUBINI 2-wire BUS present on the J2 connector. Centralized
commands are delayed by 1 second, have priority over local commands and can move the motor only
UP or DOWN. If one of the two push-buttons of the CENTR CMD is kept pressed for at least 1 second,
the motor moves in the desired direction, until the limit switch is reached.
The command is signalled to the following module through the SEQ OUT signal of the J2 connector
according to the settings of Dip Switch 2.
stop
stop
10 sec
or
stop
DOWN
CENTR CMD
1 sec
DOWN
CENTR CMD
1 sec
DSW2 ON
DSW2 OFF
DOWN
SEQ OUT
DOWN
SEQ OUT
If during the movement of a centralized command a push-button corresponding to an opposite direction
is pressed, the motor reverses the direction of rotation.
1 sec
CENTR CMD
UP
1
2
3
4
5
1
2
3
4
5
ON
ON
down
down
up
ENGLISH