GS8567-EX
GYB16.1339
IECEx
CQM11.0003
DNV11 ATEX 08693X
CZ.GS8567-EX.11(S)E-5.3/16.03
5
4
1
2
3
3
2
1
XK06-014-00557
Connections
(1)
(2).
(3).
(4).
.
This
barrier
adopts
knock
-
down
connector
with
screw
terminals
.
The
intrinsically
safe
(
IS
for
short
)
terminals
(
blue
plugs
)
should
be
connected
to
hazardous
area
devices
and
the
non
-
IS
ones
(
green
plugs
)
to
the
safe
area
devices
.
Choose
for
the
harzardous
area
the
blue
-
marked
wires.
Its
minimum
2
cross
section
area
should
be
0
.
5
mm
,
and
minimum
d
i
electric
strength
should
be
500V
.
The
wirings
in
safe
area
and
hazardous
area
must
be
separated
,
and
both
have
protection
bushes.
A
length
of
8mm
bared
wire
is
locked
by
the
M3
bolt
.
See
as
shown
below
.
Installation
The
isolated
barrier
should
be
located
at
safe
area
,
according
to
the
related
requirements
in
IEC60079
-
17
(
EN60079
-
17
)
and
IEC60079
-
19
(
EN60079
-
19
).
GS8500
-
EX
series
isolated
barrier
are
designed
for
mounting
on
35mm
DIN
guide
rail
.
Installation
according
to
the
following
steps
:
(
1
).
First
make
the
bus
-
powered
outlet
locked
into
the
guide
rail;
(
If
no
bus
-
powered
function
,
omit
this
step
)
;
(
2
).
Make
the
upside
of
the
barrier
locked
into
the
guide
rail;
(
3
).
Push
the
downside
of
the
barrier
in
the
rail
.
Disassembly
(
1
).
Insert
a
screwdriver
(
its
edge
length
≤
6mm
)
into
the
downside
metal
lock
of
the
barrier;
(
2
).
Push
the
screwdriver
upwards
,
then
prize
the
metal
lock
downwards;
(
3
).
Take
the
barrier
out
of
the
guide
rail
.
(
1
).
Before
using
,
please
check
again
whether
the
module’s Ex-proof
rating accords to the operation conditions, and
also
wiring
and
polarity
are
correct
.
(
2
).
It
is
disallowable
to
test
insulativity
among
the
terminals
with
a
megameter
.
If
necessary
,
the
wires
must
be
cut
off
before
testing
,
or
the
internal
fuse
would
blow
.
(
3
).
Every
product
has
been
test
strictly
before
leaving
factory
.
If
users
find
any
abnormality
in
the
module
,
please
contact
the
nearest
agent
or
our
company
.
(
4
).
In
5
yeras
from
the
delivery
date
,
if
the
product
works
improperly
during
normal
operation
,
we
will
repair
or
replace
it
without
payment
.
Non
-
intrinsically safe terminals
Intrinsically safe terminals
Maintenance
Add: Building 6, 201 Minyi Road, Caohejing Hi-Tech Park
Songjiang New Industrial Park, Shanghai 201612, P.R. China
Tel : +86-21-64513350 Fax : +86-21-64846984
Email
:
chenzhu
@
chenzhu
-
inst
.
com
http://www.chenzhu-inst.com
Isolated Barrier
User
Manual
Caution
Please check whether the product type on the package accords
to the ordering contract;
Read this manual carefully before installation or using. If there is
something unclear, please dial technic support hotline-400 881 0780;
Isolated barrier should be located in the safe area;
Supply voltage is 24VDC, 220VAC is forbidden;
Users are not allowed to dismantle or repair the barrier otherwise
it will induce malfunction.
Please read the instruction manual carefully before use the product,
and please safekeeping.
M3
8.0