Certifying authority: NEPSI(China)

 

Conformity

 

standards: GB3836

.

1, GB3836

.

4, GB3836

.

20, GB12476

.

and GB12476

.

4

Ex marking: 

[

Ex

 

ia Ga

]Ⅱ

C , [Ex iaD]

Maximum

 

voltage:

 

Um=250V

 

Intrinsic

 

safety

 

parameters: 

(

7

8 terminals

)

            Uo=10.5V,  Io=14mA , 

 

Po=37mW

 

          Ⅱ

C: Co=2.4

μ

F    ,  Lo=165mH

         *

B: Co

=

16

.

8

μ

F ,  Lo

=

495mH

 

          Ⅱ

A: Co

=

75

μ

F

     ,  

Lo

=

1000mH                                                      

           Note: *

B parameters are also applicable for combustible dust 

atmospheres. 

  

(

1

)

 For circuits only containing distributed capacitance and distributed

 

inductance, e

.

g

cable

allow

 

the

 

values

 

of

 

Co and Lo in accordance with 

the allowed values in the certification parameters;

 (

2

)

 For circuit combined with IS circuit and cables, if the inductance or 

capacitance  of  IS  circuit  are  no  greater  than  1%  of  the  respective 

parameters, then the permissible maximum external output parameters 

of capacitance and inductance in accordance with the allowed values in 

the certification parameters;

  (

3

)

  For  circuit  combined  with  inductance  and  capacitance,  if  both 

parameters  are  greater  than  1%  of  the  output  parameters  (excluding 

cables),  then  the  permissible  maximum  external  output  parameters  of 

capacitance and inductance should be 50% of the allowed values in the 

certification parameters.

      When  using  the  values  of  maximum  external  capacitance  (Co)  and 

inductance (Lo), please attend the following requirements:

Application

Dimensions

118.9mm×106.0mm×12.5mm

Note: Bus-powered function is optional.

1

2

3

Safe-area

Hazardous

-

area

Number

 

of

 

channels: 1/2  

Supply

 

voltage: 20~35V DC

Current

 

consumption: 

40mA(at

 

24Vdc

 

supply

output relay

 

energized

)

Safe-area relay output: 

      

Response

 

time: 

10ms

  

    Contact loading: 250V AC, 2A or 30V DC, 2A

      Load

 

type: 

 

resistive

 

load

Hazardous

-

area

 

input: 

 

     

Signal: dry contact

 

or

 

NAMUR

 

Proximity

 

Detector

      

Open Circuit Voltage

8V

      Short Circuit Current

8mA

Input  and  output  characteristics  (K1~K4  are  separately  set  to  ON,  ON, 

OFF, OFF state)

:

   

       Note: 1) K2~K4 are separately set to ON, OFF, OFF.

                   2) Dy contact switch inputs need to connect according to the                                   

                        way of Switch ( ).

Power

 

supply

 

protection: Power supply reverse

 

protection

EMC: 

According

 

to IEC 

-

/

Dielectric strength: 

       Between non

-

IS

 

part

 

and

 

IS

 

part

2500VAC

 

       Between

 

power

 

supply

 

part

 

and

 

output

 

part

500VAC

  

Insulation resistance: 

       Between non

-

IS

 

part and IS

 

part

100M

Ω

       Between

 

power

 

supply

 

part

 

and

 

output

 

part

100M

Ω

Weight: Approx

.

100g

Suitable

 

location:  Mounting  in  safe  area,  and  connected  to  the  IS

       apparatus in hazardous area up to zone 0  IIC and zone 20  IIIC.

Suitable

 

field

 

apparatus: 

     

Dry contact or DIN19234 standard NAMUR proximity switch input field 

devices(including  the  intrinsically  safe  type  pressure  switch, 

temperature switches, liquid level switch).

Function of the DIP Switch

61326 1

(

GB T 18268)

IN

OUT

Intrinsic Safety Certification     

Specification     

Intrinsic Safety Explosion Protection System     

Switch

(

)

Proximity
switch

Power supply

Power bus

6
5

8 (-)

7 (+)

2(-)

1(+)

7

8

4
3

OUT

LFD

- +

680

Ω

22k

Ω

GS8512-EX.12

Input signal

Input

2.1mA 

Input

1.2mA

Input breakage 

Input short-circuits

Output relay

LFD relay

Sta.

OFF

ON

OFF

OFF

ON

Yellow LED OFF

ON

OFF

Yellow LED ON

OFF

Red LED ON

Red LED ON

Function

ON

OFF

K1

Inverted Phase

Normal Phase

115.1mm

118.9mm

12.5mm

99mm

Summarize 

Ambient Conditions     

    Digital input, relay output isolated

 

barrier, transfers digital signals (dry 

contact  or  NAMUR  proximity  switch)  from  hazardous

 

area  to  safe  area. 

The  output  can  be  provided  to  select  phase  reversal  and  to  enable  the 

line  fault  detection.  The  product  needs  an  independent  power  supply 

and galvanic isolation among power supply, input and output.

      (

1

)

There should be no following substances in the air: flammable and 

explosive  substances;  medium  that  could  corrupt  the  coat  of  chrome, 

nickel  and  silver

.

  Moreover

,

  please  avoid  using  this  product  in  violent

 

quiver

impact

 

or strong electromagnetic

 

interference

 

environment.

      (

2

Operating

 

temperature

: -

20

℃~+

60

      (

3

Storage

 

temperature

: -

40

℃~+

80

      (

4

Relative

 

humidity

10

%~

90

%

     

Special

 

requirements

 

have to be

 

confirmed

 

before

 

using

 

the intrinsically

 

safety

 

explosion

 

protection  system(intrinsically  circuit)  which  connected 

by isolated

 

barrier and

 

intrinsically

 

safe

 

apparatus

 

in

 

field

     

 

(

1

)

 The EX-proof level of

 

intrinsically

 

safe

 

apparatus

 

should

 

meet

 

the

 

requirements

 

of

 

operation

 

conditions.  The  apparatus

 

should

 

pass

 

the

 

explosion

 

protection

 

test

 

and

 

get

 

the

 

certificate by authorized explosion-

proof product certification bodies

.

     

 

(

2

)

 The

 

intrinsic

 

safety

 

parameters

 

of

 

isolated

 

barrier

 

and

 

intrinsically

 

safe

 

apparatus

 

both

 

are

 

clear

and

 

comply

 

with

 

GB/T

 

3836

.

15.

     (3) If any parameters are unclear, the system has to be confirmed by 

authorized explosion-proof product certification bodies

.