TANDING CLEARANCES 3.3
14
CHEMINÉES
PHILIPPE
RADIANTE 747 2V PR
FREESTANDING
A: CLEARANCES TO 50MM SKAMOL BOARD
CLEARANCES TO A SOLID BRICK/HEBEL VENEER WALL
CLEARANCES TO COMBUSTIBLES
200mm
150mm
400mm
500mm
900mm
Hearth
Combustible Wall
Combustible W
all
50mm Skamotec Board
50mm Skamotec Board
50mm
Air
Gap
50mm Air Gap
550mm
400mm
400mm
500mm
900mm
Hearth
Combustible Wall
Combustible W
all
50mm Skamotec Board
50mm Skamotec Board
The Skamol boards should extend to a minimum height of 2000mm from the hearth when using a triple skin flue kit OR all
the way to the ceiling when using a single skin flue kit (refer to page 17). When using Skamotec board with a 50mm air
gap behind, it must also be ventilated for natural air flow circulation, (refer to page 15 & 16 for ventilation requirements).
400mm
900mm
400mm
Hearth
Combustible Wall
Combustible W
all
1075mm
150mm
400mm
500mm
900mm
Hearth
Combustible Wall
Combustible W
all
Brick/Hebel
Brick/Hebel
A minimum 110mm solid brick/hebel thick wall should extend a minimum height of 2000mm from the hearth when
using a triple skin flue kit or to the ceiling when using a single skin flue kit.
NON-COMBUSTIBLE CEILING:
For freestanding installations where the ceiling height is
less than 3 metres from the hearth, a non-combustible
board must be used on the ceiling and must extend
450mm in all directions from the flue outer casing,
unless forming an abutment with a wall. This can be
made of a minimum 8mm cement sheet or equivalent.
GLASS CLEARANCE:
A minimum 1500mm from the front
glass to any combustible surfaces must be maintained.
150mm
CORNER CLEARANCES:
The same rear clearance
as depicted in these illustrations applies from the two
furtherest back corner points of the fireplace to each
corner wall. Base/hearth size remains the same (page 13)
B: CLEARANCES TO 50MM SKAMOL BOARD + AIR GAP
CLEARANCES TO A SOLID BRICK OR HEBEL WALL
400mm
500mm
900mm
Hearth
Brick/Hebel
Brick/Hebel
100mm
400mm
100mm
Combustible
Material
(Refer to page 13)
(Refer to page 13)
(Refer to page 13)
(Refer to page 13)
(Refer to page 13)
*All clearances are for both FD (left) or FG (right) glass sided models