5.6.

REINITIALISING THE INSTRUMENT

To reinitialise all the test parameters, please follow the procedure below:

1. Switch off the instrument by setting the ON/OFF key to the OFF position.

2. Press the SET UP key and keep it pressed while switching on the instrument.

Machine Tester followed by Hard Reset are displayed for a few moments, then the main menu opens.

NOTES : 

The

 

reinitialised values of the adjustable parameters correspond to the requirements of standard EN 60204.

List of the test parameters per function, with their initial value.

Function

Parameter

Range of adjustment

Initial value

or possible values

U

N

Test voltage

1, 1.25, 1.5 kV AC

1 kV

1, 3, 5, 10, 20, 30, 40, 50, 60, 70,

HV

Imax

Tripping current

80, 90, 100, 150, 200, 250, 300,

500 mA

333, 350, 400, 450, 500 mA

t

Timer

1s...1min...5 min (in steps of 1 s and 10 s)

1 s

U

U

max

Max permitted

5.0 V (0.50 mm

2

), 5.0 V (0.75 mm

2

),

voltage drop

 3.3 V (1.0 mm

2

), 2.6 V (1.5 mm

2

),

3.3 V (1.0 mm

2

)

1.9 V (2.5 mm

2

), 1.4 V (4.0 mm

2

),

1.0 V 

 6.0 mm

2

t

Timer

1 s...15 s

10 s

10A

 AC

R

max

Max permitted

10 m

...1000 m

 (in steps of 10 m

)

*m

resistance

or 

*

m

 (no limit)

t

Timer

1s...15 s

10 s

U

N

Test voltage

500, 1000 V DC

500 V DC

R

min

min. allowed

0.2 M

...1 M

 (in steps of 0.1 M

)

M

insulation

1 M

...10 M

 (in steps of 1 M

)

1 M

resistance

  10 M

...500 M

 (in steps of 10 M

)

or 

*

 (no limit)

t

Timer

2 s...1min...10 min (in steps of 1 s and 10 s)

15 s

t

Syst

Measuring

2-point (1 s), 4-point (5 s)

2-point (1 s)

system

t

Timer

ON ou OFF

ON

ON/OFF (M/A)

Toutes

Baud

Baud rate

300, 600, 1200, 2400, 4800

4800

fonctions

Buzzer

ON/OFF

ON

Contrast

0%...100% (in steps of 2%)

50%

To reinitialise all the test parameters and erase all stored data, please follow the procedure below :

1. Switch off the instrument by setting the ON/OFF key to the OFF position.
2. Press the SET UP and MEM/MR keys and keep them pressed while switching on the instrument.

Machine Tester then Hard Reset followed by Clear Memory are displayed for a few moments, then the main menu opens.

NOTES :

The

 

reinitialised values of the adjustable parameters correspond to the previous table, in accordance with

standard EN 60204.

Содержание C.A 6121

Страница 1: ...150M U 513V 9min 59s M 113 5 Timer Rmin Un n n n n n CONTROLEUR MACHINE n n n n n MACHINE TESTER n n n n n MASCHINEN TESTER n n n n n MACHINE TESTER n n n n n COMPROBADOR DE MAQUINARIA ELECTRICA User...

Страница 2: ...es Use connection accessories whose overvoltage category and service voltaage are greater than or equal to those of the circuits on which the measurements are made Only use accessories that conform to...

Страница 3: ...al specifications 32 4 MEASUREMENTS 32 4 1 Dielectric test 32 4 2 Voltage drop scaled to 10 A position U 34 4 3 Low resistance position R10A 35 4 4 Insulation resistance 36 4 5 Discharge time 2 pole s...

Страница 4: ...of 1500 V AC Voltage drop scaled to 10 A AC with a test voltage of 12 V 10 A AC Low resistance with a test voltage of 12 V 10 A AC Insulation resistance with a test voltage of 500 V DC Insulation res...

Страница 5: ...TECHNICAL SPECIFICATIONS 3 1 DIELECTRIC TEST POSITION HV Nominal test voltage adjustable 1000 1250 or 1500 V 50 Hz Test voltage 1000 V 1250 V or 1500 V 50 Hz at Umains 230 V and a power Pload 500 VA...

Страница 6: ...nt 0 0 5 10 A AC Timer adjustable from 1 to 15 s resolution 1s or without timer Connection system 4 wire 3 3 LOW RESISTANCE POSITION R10A Resistance readout Range R Resolution m Accuracy 0 999 m 1 2 o...

Страница 7: ...2 counts 20 0 199 9 100 200 500 1000 10 rdg automatic ranges Range 0 200 M stable result even on a capacitive load Nominal voltage 1000 V DC 10 0 Short circuit current 1 4 mA max Measurement current...

Страница 8: ...Dimensions W x H x L 400 x 260 x 250 mm Weight 11 kg Protection index IP 40 open IP54 closed Working temperature range 0 50 C Reference temperature range 5 35 C Storage temperature range 10 60 C Max...

Страница 9: ...bove the mA unit Press EXIT key to exit this menu Tripping out current fig 6 Press I key to open the tripping out current selection menu Press the or keys to choose the tripping current Press EXIT key...

Страница 10: ...es equipped with longer cables 6 m When the test current is greater than the pre set limit the HT generator trips automatically when this value is exceeded and the pre set limit value is displayed as...

Страница 11: ...er value Timer key to set timer value or to switch it on off Resistance main result Rmax key to set threshold resistance Fig 12 Basic screen in position R10A 2 Select the test parameters as follows Re...

Страница 12: ...Basic screen in M position 2 Select the test parameters as follows Insulation resistance threshold Press the Rmin key to access the menu for insulation resistance threshold selection Press the ou keys...

Страница 13: ...C A 6121 MACHINE TESTER OBJECT UNDER TEST MAINS TEST Fig 19 Test circuits discharge time 60 V t expected MAINS TEST input voltage disconnection voltage ideal power disconnection moment power disconnec...

Страница 14: ...voltage see fig 20 is displayed when the measurement is finished t 0 1 s is displayed under the main result and no voltage is displayed on the right of the display if the discharge time is less than...

Страница 15: ...on for each function HV function Trip out The HV generator tripped because the test current was higher than the set threshold value U function U Umax The displayed result U is higher than the set thre...

Страница 16: ...OTES A displayed result can only be saved once in order to avoid the risk of storing twice Memory save locations already occupied can be erased by saving a new result at this location The occupied loc...

Страница 17: ...NE TESTER 9 pin male connector to serial printer 2 2 3 3 5 5 front view front view Fig 29 RS232 communication cable printer C2 P2 C1 P 1 TEST MAINS TEST REMOTE CAT III 600V WARNING LAMP 12V 1 1 25 1 5...

Страница 18: ...rs 001 007 in our example will be printed when you press the START key Press the CHG key then the keys to modify the machine numbers Print all All the results will be printed when you press the START...

Страница 19: ...re of the PC to communicate with the PC Pressing the PRINT RS exits the RS 232 mode and opens the main menu Communication with the PC is then not possible NOTES Check the RS 232 format in chapter 3 6...

Страница 20: ...1 9 V 2 5 mm2 1 4 V 4 0 mm2 1 0 V 6 0 mm2 t Timer 1 s 15 s 10 s R 10A AC Rmax Max permitted 10 m 1000 m in steps of 10 m m resistance or m no limit t Timer 1s 15 s 10 s UN Test voltage 500 1000 V DC...

Страница 21: ...time set up menu is not running 5 7 3 Warning buzzer One of the functions of the warning buzzer is to provide audible information relating to the evaluation of the measurement result set threshold val...

Страница 22: ...III 600V TEST MAINS TEST REMOTE WARNING LAMP 12V 1 1 25 1 5 kV START STOP TEST ON 230V 50Hz 500VA RS232C MEM MR PRINT RS SET UP C A 6121 MACHINE TESTER ON OFF HV MW R10A Dt DU ARNOUX CHAUVIN INSULATI...

Страница 23: ...USE OF WARNING LAMPS STANDARD VDE 104 The warning lamps are used to warn the user and other persons who may be present on the sites of the tests of the presence of dangerous voltages during dielectric...